1010.3.1.2 Other Than Egress Component
JUMP TO FULL CODE CHAPTER
A revolving door used as other than a component of a means of egress shall comply with Section 1010.3.1. The breakout force of a revolving door not used as a component of a means of egress shall not be more than 180 pounds (801 N).
Exception: A breakout force in excess of 180 pounds (801 N) is permitted if the breakout force is reduced to not more than 130 pounds (578 N) when not less than one of the following conditions is satisfied:
- There is a power failure or power is removed to the device holding the door wings in position.
- There is an actuation of the automatic sprinkler system where such system is provided.
- There is an actuation of a smoke detection system that is installed in accordance with Section 907 to provide coverage in areas within the building that are within 75 feet (22 860 mm) of the revolving doors.
- There is an actuation of a manual control switch, in an approved location and clearly identified, that reduces the breakout force to not more than 130 pounds (578 N).
Related Code Sections
1010.1.4.1.2 Means of Egress, Other Than Egress Component
A revolving door used as other than a component of a means of egress shall comply with Section 1010.1.4.1. The breakout force of a revolving door ...
Building Code 2018 of Illinois > 10 Means of Egress > 1010 Doors, Gates and Turnstiles > 1010.1 Doors > 1010.1.4 Special Doors > 1010.1.4.1 Revolving Doors > 1010.1.4.1.2 Other Than Egress Component
1010.3.1.2 Means of Egress, Other Than Egress Component
A revolving door used as other than a component of a means of egress shall comply with Section 1010.3.1. The breakout force of a revolving door ...
Building Code 2021 of Illinois > 10 Means of Egress > 1010 Doors, Gates and Turnstiles > 1010.3 Special Doors > 1010.3.1 Revolving Doors > 1010.3.1.2 Other Than Egress Component
1005.3.2 Means of Egress, Other Egress Components
The capacity, in inches, of means of egress components other than stairways shall be calculated by multiplying the occupant load served ...
Building Code 2018 of Illinois > 10 Means of Egress > 1005 Means of Egress Sizing > 1005.3 Required Capacity Based on Occupant Load > 1005.3.2 Other Egress Components
1005.3.2 Means of Egress, Other Egress Components
The capacity, in inches, of means of egress components other than stairways shall be calculated by multiplying the occupant load served ...
Building Code 2021 of Illinois > 10 Means of Egress > 1005 Means of Egress Sizing > 1005.3 Required Capacity Based on Occupant Load > 1005.3.2 Other Egress Components
1004.2.3 Means of Egress, Adjacent Stories
Other than for the egress components designed for convergence in accordance with Section 1005.6, the occupant load from separate stories shall ...
Building Code 2018 of Illinois > 10 Means of Egress > 1004 Occupant Load > 1004.2 Cumulative Occupant Loads > 1004.2.3 Adjacent Stories