1224.33.5 Other Space Considerations
JUMP TO FULL CODE CHAPTER
Observation rooms for the monitoring of patients up to 24 hours may be provided as a distinct unit within, the emergency department. If provided the unit shall have the following:
- Handwashing stations shall be provided in each patient room and for each four treatment stations, and for each major fraction thereof. These shall be uniformly distributed to provide equal access from each patient station. Handwashing stations shall be directly accessible to nurse stations and patient care areas.
- Each patient station shall have a minimum of 120 square feet (11.15 m2) of clear floor area including space at each bedside for visitors and provision for visual privacy from casual observation by other patients and visitors.
- One toilet room shall be provided for each six treatment stations and for each major fraction thereof.
- An administrative center/nurse station, in compliance with Section 1224.4.4.2, positioned to allow staff to observe each patient care station or room.
- A nourishment area in compliance with Section 1224.4.4.5.
Related Code Sections
1224.33.5 Interior Environment, Other Space Considerations
including space at each bedside for visitors and provision for visual privacy from casual observation by other patients and visitors. One toilet room ...
California Building Code 2016 (Vol 1 & 2) > 12 Interior Environment > 1224 [OSHPD 1] Hospitals > 1224.33 Emergency Service > 1224.33.5 Other Space Considerations
1224.33.5 Interior Environment, Other Space Considerations
including
space at each bedside for visitors and provision
for visual privacy from casual observation
by other patients and visitors.
One toilet ...
California Building Code 2019 (Vol 1 & 2) > 12 Interior Environment > 1224 [OSHPD 1] Hospitals > 1224.33 Emergency Service > 1224.33.5 Other Space Considerations
1224.33.5.1 Interior Environment, Observation Units
including
space at each bedside for visitors and provision
for visual privacy from casual observation
by other patients and visitors.
One toilet ...
California Building Code 2019 (Vol 1 & 2) > 12 Interior Environment > 1224 [OSHPD 1] Hospitals > 1224.33 Emergency Service > 1224.33.5 Other Space Considerations > 1224.33.5.1 Observation Units
17.8.3 Initiating Devices, Spacing Considerations
The location and spacing of detectors shall be the result ...
National Fire Alarm and Signaling Code 2016 of California > 17 Initiating Devices > 17.8 Radiant Energy-Sensing Fire Detectors > 17.8.3 Spacing Considerations
17.7.6 Initiating Devices, Special Considerations
other spacing adjustments required by this Code. Table 17.7.6.3.3.2 Smoke Detector Spacing Based on Air Movement (Not to Be Used for Under-Floor ...
National Fire Alarm and Signaling Code 2016 of California > 17 Initiating Devices > 17.7 Smoke-Sensing Fire Detectors > 17.7.6 Special Considerations