[BE] 1005.3.2 Other Egress Components
JUMP TO FULL CODE CHAPTER
The capacity, in inches, of means of egress components other than stairways shall be calculated by multiplying the occupant load served by such component by a means of egress capacity factor of 0.2 inches (5.1 mm) per occupant.
Exceptions:
- For other than Group H and I-2 occupancies, the capacity, in inches, of means of egress components other than stairways shall be calculated by multiplying the occupant load served by such component by a means of egress capacity factor of 0.15 inches (3.8 mm) per occupant in buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2 and an emergency voice/alarm communication system in accordance with Section 907.5.2.2.
- Facilities with smoke-protected assembly seating shall be permitted to use the capacity factors in Table 1029.6.2 indicated for level or ramped aisles for means of egress components other than stairways where the entire path for means of egress from the seating to the exit discharge is provided with a smoke control system complying with Section 909.
- Facilities with outdoor smoke-protected assembly seating shall be permitted to the capacity factors in Section 1029.6.3 indicated for level or ramped aisles for means of egress components other than stairways where the entire path for means of egress from the seating to the exit discharge is open to the outdoors.
- For Group H-1, H-2, H-3 and H-4 occupancies, the total width of means of egress in inches (mm) shall not be less than the total occupant load served by the means of egress multiplied by 0.4 inches (5.08 mm) per occupant.
- Means of egress complying with Section 1029.
Related Code Sections
1005.3.2 Means of Egress, Other Egress Components
The capacity, in inches, of means of egress components other than stairways shall be calculated by multiplying the occupant load served ...
2017 LA City Fire Code > 10 Means of Egress > 1005 Means of Egress Sizing > 1005.3 Required Capacity Based on Occupant Load > 1005.3.2 Other Egress Components
1005.3.2 Means of Egress, Other Egress Components
The capacity, in inches, of means of egress components other than stairways shall be calculated by multiplying the occupant load served ...
Los Angeles Building Code > 10 Means of Egress > 1005 Means of Egress Sizing > 1005.3 Required Capacity Based on Occupant Load > 1005.3.2 Other Egress Components
1010.1.4.1.2 Means of Egress, Other Than Egress Component
A revolving door used as other than a component of a means of egress shall comply with Section 1010.1.4.1. The breakout force of a revolving door ...
2017 LA City Fire Code > 10 Means of Egress > 1010 Doors, Gates and Turnstiles > 1010.1 Doors > 1010.1.4 Special Doors > 1010.1.4.1 Revolving Doors > 1010.1.4.1.2 Other Than Egress Component
1010.1.4.1.2 Means of Egress, Other Than Egress Component
A revolving door used as other than a component of a means of egress shall comply with Section 1010.1.4.1. The breakout force of a revolving door ...
Los Angeles Building Code > 10 Means of Egress > 1010 Doors, Gates and Turnstiles > 1010.1 Doors > 1010.1.4 Special Doors > 1010.1.4.1 Revolving Doors > 1010.1.4.1.2 Other Than Egress Component
1010.1.4.1.2 Means of Egress, Other Than Egress Component
A revolving door used as other than a component of a means of egress shall comply with Section 1010.1.4.1. The breakout force of a revolving door ...
Los Angeles Building Code > 10 Means of Egress > 1010 Doors, Gates and Turnstiles > 1010.1 Doors > 1010.1.4 Special Doors > 1010.1.4.1 Revolving Doors > 1010.1.4.1.2 Other Than Egress Component