(B) Other Circuits
JUMP TO FULL CODE CHAPTER
Any areas of ITE that require servicing of parts that are greater than 30 volts rms, 42 volts peak, or 60 volts dc shall comply with the workspace requirements of 646.19.
Informational Note No. 1: For example, field-wiring compartments for ac mains connections, power distribution units, and so forth.
Related Code Sections
604.2.14.2.1 Building Services and Systems, Other Circuits
Circuits supplying lighting for the fire command center and mechanical equipment rooms shall be transferable to the standby source ...
Minnesota Fire Code 2015 > 6 Building Services and Systems > 604 Emergency and Standby Power Systems > 604.2 Where Required > 604.2.14 High-Rise Buildings > 604.2.14.2 Separate Circuits and Luminaires > 604.2.14.2.1 Other Circuits
(2) Special Equipment, Other Circuits
For other circuits, 20 AWG copper ...
National Electrical Code 2020 of Minnesota > 6 Special Equipment > 620 Elevators, Dumbwaiters, Escalators, Moving Walks, Platform Lifts, and Stairway Chairlifts > 620.12 Minimum Size of Conductors > (A) Traveling Cables > (2) Other Circuits
(B) Special Equipment, Other Circuits
Any areas of ITE that require servicing of parts that are greater than 30 volts rms, 42 volts peak, or 60 volts dc shall comply with the workspace ...
National Electrical Code 2020 of Minnesota > 6 Special Equipment > 646 Modular Data Centers > 646.20 Working Space for ITE > (B) Other Circuits
(3) Special Equipment, Other Circuits
Circuits that do not comply with 690.9(A)(1) or (A)(2) shall be protected with one of the following methods: Conductors not greater than 3 m (10 ...
National Electrical Code 2020 of Minnesota > 6 Special Equipment > 690 Solar Photovoltaic (PV) Systems > 690.9 Overcurrent Protection > (A) Circuits and Equipment > (3) Other Circuits
(S) Special Occupancies, Prewiring for Other Circuits
Prewiring installed for the purpose of installing other appliances or devices shall comply with the applicable portions of this article ...
National Electrical Code 2020 of Minnesota > 5 Special Occupancies > 551 Recreational Vehicles and Recreational Vehicle Parks > 551.47 Wiring Methods > (S) Prewiring for Other Circuits