(I) Other Applications
JUMP TO FULL CODE CHAPTER
For other applications, conductors of Class 2 and Class 3 circuits shall be separated by at least 50 mm (2 in.) from conductors of any electric light, power, Class 1 non-power-limited fire alarm or medium power network-powered broadband communications circuits unless one of the following conditions is met:
- Either all of the electric light, power, Class 1, non-powerlimited fire alarm and medium-power network-powered broadband communications circuit conductors or all of the Class 2 and Class 3 circuit conductors are in a raceway or in metal-sheathed, metal-clad, nonmetallic-sheathed, Type TC, or Type UF cables
- All of the electric light, power, Class 1 non-power-limited fire alarm, and medium-power network-powered broadband communications circuit conductors are permanently separated from all of the Class 2 and Class 3 circuit conductors by a continuous and firmly fixed nonconductor, such as porcelain tubes or flexible tubing, in addition to the insulation on the conductors
Related Code Sections
17.6.3.7 Initiating Devices, Other Applications
Where a detector is used in an application other than open area protection, the manufacturer's published instructions shall be followed ...
National Fire Alarm and Signaling Code 2016 of Minnesota > 17 Initiating Devices > 17.6 Heat-Sensing Fire Detectors > 17.6.3 Location and Spacing > 17.6.3.7 Other Applications
5703.1.3 Flammable and Combustible Liquids, Other Applications
The fire code official is authorized to determine the extent of the Class I electrical equipment and wiring location when a condition ...
Minnesota Fire Code 2015 > 57 Flammable and Combustible Liquids > 5703 General Requirements > 5703.1 Electrical > 5703.1.3 Other Applications
5703.1.3 Flammable and Combustible Liquids, Other Applications
The fire code official is authorized to determine the extent of the Class I electrical equipment and wiring location where a condition ...
2020 Minnesota State Fire Code > 57 Flammable and Combustible Liquids > 5703 General Requirements > 5703.1 Electrical > 5703.1.3 Other Applications
(I) Special Conditions, Other Applications
For other applications, conductors of Class 2 and Class 3 circuits shall be separated by at least 50 mm (2 in.) from conductors of any electric light ...
National Electrical Code 2020 of Minnesota > 7 Special Conditions > 725 Class 1, Class 2, and Class 3 Remote- Control, Signaling, and Power-Limited Circuits > 725.136 Separation From Electric Light, Power, Class 1, Non- Power-Limited Fire Alarm Circuit Conductors, and Medium- Power Network-Powered Broadband Communications Cables > (I) Other Applications
(G) Special Conditions, Other Applications
For other applications, power-limited fire alarm circuit conductors shall be separated by at least 50 mm (2 in.) from conductors of any electric ...
National Electrical Code 2020 of Minnesota > 7 Special Conditions > 760 Fire Alarm Systems > 760.136 Separation From Electric Light, Power, Class 1, NPLFA, and Medium-Power Network-Powered Broadband Communications Circuit Conductors > (G) Other Applications