[F] 907.2.21.2 Other Airport Traffic Control Towers
JUMP TO FULL CODE CHAPTER
Airport traffic control towers with a single exit or where sprinklers are not installed throughout shall be provided with smoke detectors in all of the following locations:
- Airport traffic control cab.
- Electrical and mechanical equipment rooms.
- Airport terminal radar and electronics rooms.
- Office spaces incidental to the tower operation.
- Lounges for employees, including sanitary facilities.
- Means of egress.
- Utility shafts where access to smoke detectors can be provided.
Related Code Sections
907.2.21.2 Fire Protection and Life Safety Systems, Other Airport Traffic Control Towers
Airport traffic control towers with a single exit or where sprinklers are not installed throughout shall be provided with smoke detectors in all ...
Building Code 2018 of Illinois > 9 Fire Protection and Life Safety Systems > 907 Fire Alarm and Detection Systems > 907.2 Where Required—New Buildings and Structures > 907.2.21 Airport Traffic Control Towers > 907.2.21.2 Other Airport Traffic Control Towers
907.2.22.2 Fire Protection and Life Safety Systems, Other Airport Traffic Control Towers
Airport traffic control towers with a single exit or where sprinklers are not installed throughout shall be provided with smoke detectors in all ...
Building Code 2021 of Illinois > 9 Fire Protection and Life Safety Systems > 907 Fire Alarm and Detection Systems > 907.2 Where Required—New Buildings and Structures > 907.2.22 Airport Traffic Control Towers > 907.2.22.2 Other Airport Traffic Control Towers
412.2 Special Detailed Requirements Based on Occupancy and Use, Airport Traffic Control Towers
The provisions of Sections 412.2.1 through 412.2.6 shall apply to airport traffic control towers occupied only for the following uses: Airport ...
Building Code 2018 of Illinois > 4 Special Detailed Requirements Based on Occupancy and Use > 412 Aircraft-Related Occupancies > 412.2 Airport Traffic Control Towers
412.2 Special Detailed Requirements Based on Occupancy and Use, Airport Traffic Control Towers
The provisions of Sections 412.2.1 through 412.2.6 shall apply to airport traffic control towers occupied only for the following uses: Airport ...
Building Code 2021 of Illinois > 4 Special Detailed Requirements Based on Occupancy and Use > 412 Aircraft-Related Occupancies > 412.2 Airport Traffic Control Towers
304.2 Occupancy Classification and Use, Airport Traffic Control Towers
Airport traffic control towers shall comply with Section 412.2 ...
Building Code 2021 of Illinois > 3 Occupancy Classification and Use > 304 Business Group B > 304.2 Airport Traffic Control Towers