Section 2408 Organic Peroxides and Dual-Component Coatings
JUMP TO FULL CODE CHAPTER
Spraying operations involving the use of organic peroxides and other dual-component coatings shall be in accordance with the requirements of Section 2403 and Sections 2408.2 through 2408.5.
Spraying operations involving the use of organic peroxides and other dual-component coatings shall be conducted in approved sprinklered spray booths complying with Section 2404.3.3.
Spray guns and related handling equipment used with organic peroxides shall be of a type manufactured for such use.
Separate pressure vessels and inserts specifically for the application shall be used for the resin and for the organic peroxide, and shall not be interchanged. Organic peroxide pressure tank inserts shall be constructed of stainless steel or polyethylene.
Organic peroxide initiators shall not be contaminated with foreign substances.
Spilled organic peroxides shall be promptly removed and any residue thereof promptly eliminated. Spilled material absorbed by using a noncombustible absorbent shall be promptly disposed of in accordance with the manufacturer's recommendation.
Materials shall not be contaminated by dusts and overspray residues resulting from the sanding or spraying of finishing materials containing organic peroxides.
Handling of organic peroxides shall be conducted in a manner that avoids shock and friction that produces decomposition and violent reaction hazards.
Organic peroxides shall not be mixed directly with accelerators or promoters.
Personnel working with organic peroxides and dual-component coatings shall be specifically trained to work with these materials.
The storage of organic peroxides shall comply with Chapter 62.
Only nonsparking tools shall be used in areas where organic peroxides are stored, mixed or applied.
Related Code Sections
Section 2408 Flammable Finishes, Organic Peroxides and Dual-Component Coatings
Spraying operations involving the use of organic peroxides and other dual-component coatings shall be in accordance with the requirements of Section ...
Fire Code 2021 of Colorado > 24 Flammable Finishes > 2408 Organic Peroxides and Dual-Component Coatings
Section 2408 Flammable Finishes, Organic Peroxides and Dual-Component Coatings
Spraying operations involving the use of organic peroxides and other dual-component coatings shall be in accordance with the requirements of Section ...
Fire Code 2018 of Colorado > 24 Flammable Finishes > 2408 Organic Peroxides and Dual-Component Coatings
2408.3 Flammable Finishes, Equipment
Spray guns and related handling equipment used with organic peroxides shall be of a type manufactured for such use ...
Fire Code 2018 of Colorado > 24 Flammable Finishes > 2408 Organic Peroxides and Dual-Component Coatings > 2408.3 Equipment
2408.1 Flammable Finishes, General
Spraying operations involving the use of organic peroxides and other dual-component coatings shall be in accordance with the requirements of Section ...
Fire Code 2021 of Colorado > 24 Flammable Finishes > 2408 Organic Peroxides and Dual-Component Coatings > 2408.1 General
2408.1 Flammable Finishes, General
Spraying operations involving the use of organic peroxides and other dual-component coatings shall be in accordance with the requirements of Section ...
Fire Code 2018 of Colorado > 24 Flammable Finishes > 2408 Organic Peroxides and Dual-Component Coatings > 2408.1 General