Section 418 Organic Coatings

Building Code 2015 of Utah > 4 Special Detailed Requirements Based on Use and Occupancy > 418 Organic Coatings
JUMP TO FULL CODE CHAPTER

418.1 Building Features

Manufacturing of organic coatings shall be done only in buildings that do not have pits or basements.

418.2 Location

Organic coating manufacturing operations and operations incidental to or connected therewith shall not be located in buildings having other occupancies.

418.3 Process Mills

Mills operating with close clearances and that process flammable and heat-sensitive materials, such as nitrocellulose, shall be located in a detached building or noncombustible structure.

418.4 Tank Storage

Storage areas for flammable and combustible liquid tanks inside of structures shall be located at or above grade and shall be separated from the processing area by not less than 2-hour fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 711, or both.

418.5 Nitrocellulose Storage

Nitrocellulose storage shall be located on a detached pad or in a separate structure or a room enclosed with not less than 2-hour fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 711, or both.

418.6 Finished Products

Storage rooms for finished products that are flammable or combustible liquids shall be separated from the processing area by not less than 2-hour fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 711, or both.
Share URL

Copy and paste the link below into emails, chats or browsers.

Copy

You can also copy or bookmark the link from your browser's address bar.

Related Code Sections


Section 418 Special Detailed Requirements Based on Occupancy and Use, Organic Coatings
Manufacturing of organic coatings shall be done only in buildings that do not have pits or basements ...
Building Code 2018 of Utah > 4 Special Detailed Requirements Based on Occupancy and Use > 418 Organic Coatings
Section 418 Special Detailed Requirements Based on Use and Occupancy, Organic Coatings
Organic coating manufacturing operations and operations incidental ...
Building Code 2015 of Utah > 4 Special Detailed Requirements Based on Use and Occupancy > 418 Organic Coatings
502.12 Exhaust Systems, Organic Coating Processes
Enclosed structures involving organic coating processes in which Class I liquids are processed or handled shall be ventilated at a rate of not less ...
Mechanical Code 2015 of Utah > 5 Exhaust Systems > 502 Required Systems > 502.12 Organic Coating Processes
502.12 Exhaust Systems, Organic coating processes
Enclosed structures involving organic coating processes in which Class I liquids are processed or handled shall be ventilated at a rate of not less ...
Mechanical Code 2018 of Utah > 5 Exhaust Systems > 502 Required Systems > 502.12 Organic coating processes
418.3 Special Detailed Requirements Based on Use and Occupancy, Process Mills
Mills operating with close clearances and that process flammable and heat-sensitive materials, such as nitrocellulose, shall be located in a detached ...
Building Code 2015 of Utah > 4 Special Detailed Requirements Based on Use and Occupancy > 418 Organic Coatings > 418.3 Process Mills
About UpCodes

UpCodes provides an intuitive resource to navigate building regulations.

Codes are organized by jurisdiction to help you understand which regulations apply to your project.


Find Your Codes
COMPANY INFO About Free Law Contact Careers Terms Privacy Press Kit
CATEGORY General New York City New York State California Codes Building Codes Online
PREMIUM Features Pricing Sign Up Log In
CODES IBC 2015 IRC 2015 IPC 2015 California Building Code 2016 Popular Sections

FOLLOW US