1926.652(b)(1) Option (1)-Allowable Configurations and Slopes
JUMP TO FULL CODE CHAPTER
Excavations shall be sloped at an angle not steeper than one and one-half horizontal to one vertical (34 degrees measured from the horizontal), unless the employer uses one of the other options listed below.
Slopes specified in paragraph (b)(1)(i) of this section, shall be excavated to form configurations that are in accordance with the slopes shown for Type C soil in appendix B to this subpart.
Related Code Sections
1926.652(b)(1) Excavations, Option (1)-Allowable Configurations and Slopes
Slopes specified in paragraph (b)(1)(i) of this section, shall be excavated to form configurations that are in accordance with the slopes ...
OSHA 1926 Construction > P Excavations > 1926.652 Requirements for Protective Systems > 1926.652(b) Design of Sloping and Benching Systems > 1926.652(b)(1) Option (1)-Allowable Configurations and Slopes
Subpart P Excavations, App B - Sloping and Benching
Configurations of sloping and benching systems shall be in accordance with Figure B-1.
TABLE B-1
MAXIMUM ALLOWABLE SLOPES
SOIL ...
1926.652(b)(4) Excavations, Option (4)-Design by a Registered Professional Engineer
Sloping and benching systems not utilizing Option (1) or Option (2) or Option (3) under paragraph (b) of this section shall be approved ...
OSHA 1926 Construction > P Excavations > 1926.652 Requirements for Protective Systems > 1926.652(b) Design of Sloping and Benching Systems > 1926.652(b)(4) Option (4)-Design by a Registered Professional Engineer
1926.652(b)(3) Excavations, Option (3)-Designs Using Other Tabulated Data
; Identification of the limits of use of the data, to include the magnitude and configuration of slopes determined to be safe ...
OSHA 1926 Construction > P Excavations > 1926.652 Requirements for Protective Systems > 1926.652(b) Design of Sloping and Benching Systems > 1926.652(b)(3) Option (3)-Designs Using Other Tabulated Data
1926.652(b)(3)(ii)(B) Excavations,
Identification of the limits of use of the data, to include the magnitude and configuration of slopes determined to be safe; ...
OSHA 1926 Construction > P Excavations > 1926.652 Requirements for Protective Systems > 1926.652(b) Design of Sloping and Benching Systems > 1926.652(b)(3) Option (3)-Designs Using Other Tabulated Data > 1926.652(b)(3)(ii) > 1926.652(b)(3)(ii)(B)