1203.5 Operational Inspection and Testing
JUMP TO FULL CODE CHAPTER
Emergency power systems, including all appurtenant components, shall be inspected and tested under load in accordance with NFPA 110 and NFPA 111.
Exception: Where the emergency power system is used for standby power or peak load shaving, such use shall be recorded and shall be allowed to be substituted for scheduled testing of the generator set, provided that appropriate records are maintained.
In Group I-2 occupancies, emergency and standby power systems shall be inspected and tested under load in accordance with NFPA 99.
The test of the transfer switch shall consist of electrically operating the transfer switch from the normal position to the alternate position and then return to the normal position.
Related Code Sections
1203.5 Energy Systems, Operational Inspection and Testing
Emergency power systems, including all appurtenant components, shall be inspected and tested under load in accordance with NFPA 110 and NFPA 111 ...
Fire Code 2021 of Colorado > 12 Energy Systems > 1203 Emergency and Standby Power Systems > 1203.5 Operational Inspection and Testing
1203.5 Energy Systems, Operational Inspection and Testing
Emergency power systems, including all appurtenant components, shall be inspected and tested under load in accordance with NFPA 110 and NFPA 111 ...
Fire Code 2018 of Colorado > 12 Energy Systems > 1203 Emergency and Standby Power Systems > 1203.5 Operational Inspection and Testing
1207.2.2.1 Energy Systems, Ongoing Inspection and Testing
and the operation and maintenance manual. Inspection and testing records shall be maintained in the operation and maintenance manual ...
Fire Code 2021 of Colorado > 12 Energy Systems > 1207 Electrical Energy Storage Systems (ESS) > 1207.2 Commissioning, Decommissioning, Operation and Maintenance > 1207.2.2 Operation and Maintenance > 1207.2.2.1 Ongoing Inspection and Testing
26.9.1 Marine Systems,
Instructions for operation, inspection, maintenance, and testing shall be kept on the vessel ...
Standard for the Installation of Sprinkler Systems 2013 of Colorado > 26 Marine Systems > 26.9 System Instructions and Maintenance > 26.9.1
26.9.1 Marine Systems,
Instructions for operation, inspection, maintenance, and testing shall be kept on the vessel ...
Standard for the Installation of Sprinkler Systems 2016 of Colorado > 26 Marine Systems > 26.9 System Instructions and Maintenance > 26.9.1