23.16.4.9 Operation of Class B Radio Pathways
Go To Full Code Chapter
23.16.4.9.1
Radio frequency pathways designated as Class B shall operate as follows:
- A redundant path is not included.
- Operational capability is verified via end-to-end communication.
- Conditions that affect the intended operation of the pathway are annunciated as a trouble signal.
- Operational capability stops at the affected portion of the pathway.
- Each transceiver and/or repeater in a radio frequency pathway is powered by one of the following means:
- Both a primary and a secondary source meeting Section 10.6
- Multiple primary batteries meeting 23.16.2.2
23.16.4.9.2
Where operational capability is to be maintained during a fault, the operational capability shall be restored within 200 seconds of the application of the fault.
Related Code Sections
23.16.4.9 Protected Premises Alarm and Signaling Systems, Operation of Class B Radio Pathways
Radio frequency pathways designated as Class B shall operate as follows: A redundant path is not included. Operational capability is verified via ...
12.3.2 Circuits and Pathways, Class B
A pathway shall be designated as Class B when it performs as follows: It does not include a redundant path. Operational capability stops ...
12.3.2 Circuits and Pathways, Class B
A pathway shall be designated as Class B when it performs as follows: It does not include a redundant path. Operational capability stops ...
23.16.4.8.1 Protected Premises Alarm and Signaling Systems,
Radio frequency pathways designated as Class A shall operate as follows: A redundant pathway is included. Operational capability is verified via ...
3.3.188 Definitions, Pathway Survivability
The ability of any conductor, optic fiber, radio carrier, or other means for transmitting system information to remain operational during fire ...