7.1.4 Openings at Shear Walls
JUMP TO FULL CODE CHAPTER
Diaphragm openings immediately adjacent to the shear walls constitute less than 25 percent of the wall length, and the available length appears sufficient.
For conforming buildings, the evaluator may consider this condition as mitigated, and no calculations are necessary. The deficiency is in the length of diaphragm needed to transfer shear to the wall or frame and to provide lateral support for the wall or frame.
Procedure for diaphragm shear: Verify that there is a path of forces and sufficient strength to deliver the diaphragm shear to the shear wall. The diaphragm shear is the demand.
Procedure for lateral support of the wall: Treat the wall as a portion of the building using Fp as the demand.
Related Code Sections
7.1.4 Seismic Evaluation Procedures for Hospital Buildings, Openings at Shear Walls
Diaphragm openings immediately adjacent to the shear walls constitute less than 25 percent of the wall length, and the available length appears ...
California Administrative Code 2019 > 6 Seismic Evaluation Procedures for Hospital Buildings > 7 Procedures for Diaphragms > 7.1 Diaphragms > 7.1.4 Openings at Shear Walls
7.1.4 Seismic Evaluation Procedures for Hospital Buildings, Openings at Shear Walls
Diaphragm openings immediately adjacent to the shear walls constitute less than 25 percent of the wall length, and the available length appears ...
California Administrative Code 2016 > 6 Seismic Evaluation Procedures for Hospital Buildings > 7 Procedures for Diaphragms > 7.1 Diaphragms > 7.1.4 Openings at Shear Walls
7.1 Seismic Evaluation Procedures for Hospital Buildings, Diaphragms
Diaphragm openings immediately adjacent to the shear walls constitute less than 25 percent of the wall length, and the available length appears ...
California Administrative Code 2016 > 6 Seismic Evaluation Procedures for Hospital Buildings > 7 Procedures for Diaphragms > 7.1 Diaphragms
A112.2.2 Guidelines for the Seismic Retrofit of Existing Buildings, Shear Walls With Openings
Wall piers shall be analyzed according to the following procedure, which is diagramed in Figure A1-2. For any pier, 1.1. The pier shear ...
California Existing Building Code 2016 > A Guidelines for the Seismic Retrofit of Existing Buildings > A112 Analysis and Design > A112.2 Existing Unreinforced Masonry Walls > A112.2.2 Shear Walls With Openings
A112.2.2 Guidelines for the Seismic Retrofit of Existing Buildings, Shear Walls With Openings
Wall piers shall be analyzed according to the following procedure, which is diagrammed in Figure A112.2.2. For any pier, 1.1. The pier shear ...
California Existing Building Code 2019 > A Guidelines for the Seismic Retrofit of Existing Buildings > A112 Analysis and Design > A112.2 In-Plane Shear of Unreinforced Masonry Walls > A112.2.2 Shear Walls With Openings