• Codes
  • Features

    Features Overview

    Go to features
    Reference

    Reference.

    A reliable and up-to-date source of codes.
    Research

    Research.

    Rapidly and efficiently calculate project parameters.
    Collaboration

    Collaboration.

    Get everyone on the same page and streamline code research.
    Workflows
    Architects
    Architects
    General Contractors
    General Contractors
    Building Official & Plans Examiners
    Building Official & Plans Examiners
    Inspectors
    Inspectors
    Owners
    Owners
    Subcontractors
    Subcontractors
    Code Consultants
    Code Consultants
  • Pricing
  • Login
  • Sign Up
Sign Up
Login
  • Code Library
  • Features
  • Pricing
  • About
  • Careers
  • Help
  • Contact
  • Terms
  • Privacy
Sign Up
Upgrade to Premium
Code calculators: Code Calculators automatically generates a detailed list of requirements.
REFERENCE
Amendment Styling
Industry-leading search
Code diagrams
RESEARCH
Code calculators
Filter by topic
Code compare
Code sheet exports
COLLABORATION
Team projects
Bookmarks
Comments
START 2 WEEK FREE TRIAL
Have an account? Sign in
// CODE SNIPPET

Section 716 Opening Protectives

Building Code 2021 of Illinois > 7 Fire and Smoke Protection Features > 716 Opening Protectives
JUMP TO FULL CODE CHAPTER
ILLUSTRATION

716.1 General

Opening protectives required by other sections of this code shall comply with the provisions of this section and shall be installed in accordance with NFPA 80.
TABLE 716.1(1)
MARKING FIRE-RATED GLAZING ASSEMBLIES
FIRE TEST STANDARD MARKING DEFINITION OF MARKING
ASTM E119 or UL 263 W Meets wall assembly criteria.
ASTM E119 or UL 263 FC Meets floor/ceiling criteriaa
NFPA 257 or UL 9 OH Meets fire window assembly criteria including the hose stream test.
NFPA 252 or UL 10B or UL 10C D Meets fire door assembly criteria.
H Meets fire door assembly hose stream test.
T Meets 450°F temperature rise criteria for 30 minutes
— XXX The time in minutes of the fire resistance or fire protection rating of the glazing assembly.
For SI: °C = [(°F) — 32]/1.8.
  1. See Section 2409.1
TABLE 716.1(2)
OPENING FIRE PROTECTION ASSEMBLIES, RATINGS AND MARKINGS
TYPE OF ASSEMBLY REQUIRED WALL ASSEMBLY RATING (hours) MINIMUM FIRE DOOR AND FIRE SHUTTER ASSEMBLY RATING (hours) DOOR VISION PANEL SIZEa FIRE-RATED GLAZING MARKING DOOR VISION PANELb,c MINIMUM SIDELIGHT/TRANSOM ASSEMBLY RATING (hours) FIRE-RATED GLAZING MARKING SIDELIGHT/TRANSOM PANEL
Fire protection Fire resistance Fire protection Fire resistance
Fire walls and fire barriers having a required fire-resistance rating greater than 1 hour 4 3 See Note a D-H-W-240 Not Permitted 4 Not Permitted W-240
3 3d See Note a D-H-W-180 Not Permitted 3 Not Permitted W-180
2 11/2 100 sq. in. ≤100 sq. in. = D-H-90

>100 sq. in.=D-H-W-90
Not Permitted 2 Not Permitted W-120
11/2 11/2 100 sq. in. ≤100 sq. in. = D-H-90

>100 sq. in.= D-H-W-90
Not Permitted 11/2 Not Permitted W-90
Double fire walls constructed in accordance with NFPA 221 Single-wall assembly rating (hours)e Each wall of the double-wall assembly (hours)f —
4 3 3 See Note a D-H-W-180 Not Permitted 3 Not Permitted W-180
3 2 11/2 100 sq. in. ≤ 100 sq. in. = D-H-90

>100 sq. in.= D-H-W-90
Not Permitted 2 Not Permitted W-120
2 1 1 100 sq. in. < 100 sq. in. = D-H-60

> 100 sq. in. = D-H-W-60
Not Permitted 1 Not Permitted W-60
Enclosures for shafts, interior exit stairways and interior exit ramps. 2 11/2 100 sq. in.b ≤100 sq. in. = D-H-90

> 100 sq. in.= D-H-T-W-90
Not Permitted 2 Not Permitted W-120
Horizontal exits in fire wallsg 4 3 100 sq. in. ≤100 sq. in. = D-H-180

> 100 sq. in.=D-H-W-240
Not Permitted 4 Not Permitted W-240
3 3d 100 sq. in. ≤100 sq. in. = D-H-180

> 100 sq. in.=D-H-W-180
Not Permitted 3 Not Permitted W-180
Fire barriers having a required fire-resistance rating of 1 hour: Enclosures for shafts, exit access stairways, exit access ramps, interior exit stairways and interior exit ramps; and exit passageway walls 1 1 100 sq. in. ≤100 sq. in. = D-H-60

>100 sq. in.=D-H-T-W-60
Not Permitted 1 Not Permitted W-60
  Fire protection  
Other fire barriers 1 3/4 Maximum size tested D-H 3/4h D-Hh
Fire partitions:Corridor walls 1 1/3a Maximum size tested D-20 3/4a D-H-OH-45
0.5 1/3a Maximum size tested D-20 1/3 D-H-OH-20
Other fire partitions 1 3/4i Maximum size tested D-H-45 3/4 D-H-45
0.5 1/3 Maximum size tested D-H-20 1/3 D-H-20
Exterior walls 3 11/2 100 sq. in.a ≤100 sq. in. = D-H-90

> 100 sq. in = D-H-W-90
Not Permitted 3 Not Permitted W-180
2 11/2 Maximum size tested D-H 90 or D-H-W-90 11/2h 2 D-H-OH-90h W-120
  Fire protection  
1 3/4 Maximum size tested D-H-45 3/4 h D-H-45h
Smoke barriers   Fire protection  
1 1/3 Maximum size tested D-20 3/4 D-H-OH-45
For SI: 1 square inch = 645.2 mm.
  1. Fire-resistance-rated glazing tested to ASTM E119 in accordance with Section 716.1.2.3 shall be permitted, in the maximum size tested.
  2. Under the column heading "Fire-rated glazing marking door vision panel," W refers to the fire-resistance rating of the glazing, not the frame.
  3. See Section 716.1.2.2.1 and Table 716.1(1) for additional permitted markings.
  4. Two doors, each with a fire protection rating of 11/2 hours, installed on opposite sides of the same opening in a fire wall, shall be deemed equivalent in fire protection rating to one 3-hour fire door.
  5. As required in Section 706.4.
  6. As allowed in Section 4.6 of NFPA 221.
  7. See Section 716.2.5.1.2.
  8. Fire-protection-rated glazing is not permitted for fire barriers required by Section 1207 of the International Fire Code to enclose energy storage systems. Fire-resistance-rated glazing assemblies tested to ASTM E119 or UL 263, as specified in Section 716.1.2.3, shall be permitted.
  9. Two doors, each with a fire rating of 20 minutes, installed on opposite sides of the same opening in a fire partition, shall be deemed equivalent in fire protection rating to one 45-minute fire door.
TABLE 716.1(3)
FIRE WINDOW ASSEMBLY FIRE PROTECTION RATINGS
TYPE OF WALL ASSEMBLY REQUIRED WALL ASSEMBLY RATING (hours) MINIMUM FIRE WINDOW ASSEMBLY RATING (hours) FIRE-RATED GLAZING MARKING
Interior walls      
Fire walls
All NPa W-XXXb
Fire barriers
>1 NPa W-XXXb
1 NPa W-XXXb
Atrium separations (Section 707.3.6),

Incidental use areas (Section 707.3.7),c

Mixed occupancy separations (Section 707.3.9)


1



3/4



OH-45 or W-60

Fire partitions
1 3/4 OH-45 or W-60
0.5 1/3 OH-20 or W-30
Smoke barriers
1 3/4 OH-45 or W-60
Exterior walls >1 11/2 OH-90 or W-XXXb
1 3/4 OH-45 or W-60
0.5 1/3 OH-20 or W-30
Party wall All NP Not Applicable
NP = Not Permitted.
  1. Not permitted except fire-resistance-rated glazing assemblies tested to ASTM E119 or UL 263, as specified in Section 716.1.2.3.
  2. XXX = The fire rating duration period in minutes, which shall be equal to the fire-resistance rating required for the wall assembly.
  3. Fire-protection-rated glazing is not permitted for fire barriers required by Section 1207 of the International Fire Code to enclose energy storage systems. Fire-resistance-rated glazing assemblies tested to ASTM E119 or UL 263, as specified in Section 716.1.2.3, shall be permitted.

716.1.1 Alternative Methods for Determining Fire Protection Ratings

The application of any of the alternative methods specified in this section shall be based on the fire exposure and acceptance criteria specified in NFPA 252, NFPA 257, UL 9, UL 10B or UL 10C. The required fire resistance of an opening protective shall be permitted to be established by any of the following methods or procedures:
  1. Designs documented in approved sources.
  2. Calculations performed in an approved manner.
  3. Engineering analysis based on a comparison of opening protective designs having fire protection ratings as determined by the test procedures set forth in NFPA 252, NFPA 257, UL 9, UL 10B or UL 10C.
  4. Alternative protection methods as allowed by Section 104.11.

716.1.2 Glazing

Glazing used in fire door assemblies and fire window assemblies shall comply with this section in addition to the requirements of Sections 716.2 and 716.3, respectively.

716.1.2.1 Safety Glazing

Fire-protection-rated glazing and fire-resistance-rated glazing installed in fire door assemblies and fire window assemblies shall comply with the safety glazing requirements of Chapter 24 where applicable.

716.1.2.2 Marking Fire-Rated Glazing Assemblies

Fire-rated glazing assemblies shall be marked in accordance with Tables 716.1(1), 716.1(2) and 716.1(3).

716.1.2.2.1 Fire-Rated Glazing Identification

For fire-rated glazing, the label shall bear the identification required in Tables 716.1(1) and 716.1(2). "D" indicates that the glazing is permitted to be used in fire door assemblies and meets the fire protection requirements of NFPA 252, UL 10B or UL 10C. "H" indicates that the glazing meets the hose stream requirements of NFPA 252, UL 10B or UL 10C. "T" indicates that the glazing meets the temperature requirements of Section 716.2.2.3.1. The placeholder "XXX" represents the fire-rating period, in minutes.

716.1.2.2.2 Fire-Protection-Rated Glazing Identification

For fire-protection-rated glazing, the label shall bear the following identification required in Tables 716.1(1) and 716.1(3): "OH — XXX." "OH" indicates that the glazing meets both the fire protection and the hose-stream requirements of NFPA 257 or UL 9 and is permitted to be used in fire window openings. The placeholder "XXX" represents the fire-rating period, in minutes.

716.1.2.2.3 Fire-Resistance-Rated Glazing Identification

For fire-resistance-rated glazing, the label shall bear the identification required in Section 703.4 and Table 716.1(1).

716.1.2.2.4 Fire-Rated Glazing That Exceeds the Code Requirements

Fire-rated glazing assemblies marked as complying with hose stream requirements (H) shall be permitted in applications that do not require compliance with hose stream requirements. Fire-rated glazing assemblies marked as complying with temperature rise requirements (T) shall be permitted in applications that do not require compliance with temperature rise requirements. Fire-rated glazing assemblies marked with ratings (XXX) that exceed the ratings required by this code shall be permitted.

716.1.2.3 Fire-Resistance-Rated Glazing

Fire-resistance-rated glazing tested as part of a fire-resistance-rated wall or floor/ceiling assembly in accordance with ASTM E119 or UL 263 and labeled in accordance with Section 703.4 shall not otherwise be required to comply with this section where used as part of a wall or floor/ceiling assembly.

716.1.2.3.1 Glazing in Fire Door and Fire Window Assemblies

Fire-resistance-rated glazing shall be permitted in fire door and fire window assemblies where tested and installed in accordance with their listings and where in compliance with the requirements of this section.

716.2 Fire Door Assemblies

Fire door assemblies required by other sections of this code shall comply with the provisions of this section. Fire door frames with transom lights, sidelights or both shall be permitted in accordance with Section 716.2.5.4.

716.2.1 Testing Requirements

Approved fire door and fire shutter assemblies shall be constructed of any material or assembly of component materials that conforms to the test requirements of Sections 716.2.1.1 through 716.2.1.4 and the fire protection rating indicated in Table 716.1(2).
Exceptions:
  1. Labeled protective assemblies that conform to the requirements of this section or UL 10A, UL 14B and UL 14C for tin-clad fire door assemblies.
  2. Floor fire door assemblies in accordance with Section 712.1.13.1.

716.2.1.1 Side-Hinged or Pivoted Swinging Doors

Fire door assemblies with side-hinged and pivoted swinging doors shall be tested in accordance with NFPA 252 or UL 10C. For tests conducted in accordance with NFPA 252, the fire test shall be conducted using the positive pressure method specified in the standard.

716.2.1.2 Other Types of Assemblies

Fire door assemblies with other types of doors, including swinging elevator doors, horizontal sliding fire doors, rolling steel fire doors, fire shutters, bottom- and side-hinged chute intake doors, and top-hinged chute discharge doors, shall be tested in accordance with NFPA 252 or UL 10B. For tests conducted in accordance with NFPA 252, the neutral pressure plane in the furnace shall be maintained as nearly equal to the atmospheric pressure as possible at the top of the door, as specified in the standard.

716.2.1.3 Glazing in Transoms Lights and Sidelights in Corridors and Smoke Barriers

Glazing material in any other part of the door assembly, including transom lights and sidelights, shall be tested in accordance with NFPA 257 or UL 9, including the hose stream test, in accordance with Section 716.3.1.1.

716.2.1.4 Smoke and Draft Control

Fire door assemblies that serve as smoke and draft control assemblies shall be tested in accordance with UL 1784.

716.2.2 Performance Requirements

Fire door assemblies shall be installed in the assemblies specified in Table 716.1(2) and shall comply with the fire protection rating specified.

716.2.2.1 Door Assemblies in Corridors and Smoke Barriers

ILLUSTRATION
Fire door assemblies required to have a minimum fire protection rating of 20 minutes where located in corridor walls or smoke barrier walls having a fire-resistance rating in accordance with Table 716.1(2) shall be tested in accordance with NFPA 252 or UL 10C without the hose stream test.
Exceptions:
  1. Viewports that require a hole not larger than 1 inch (25 mm) in diameter through the door, have not less than a 0.25-inch-thick (6.4 mm) glass disc and the holder is of metal that will not melt out where subject to temperatures of 1,700°F (927°C).
  2. Corridor door assemblies in occupancies of Group I-2 shall be in accordance with Section 407.3.1.
  3. Unprotected openings shall be permitted for corridors in multitheater complexes where each motion picture auditorium has not fewer than one-half of its required exit or exit access doorways opening directly to the exterior or into an exit passageway.
  4. Horizontal sliding doors in smoke barriers that comply with Sections 408.6 and 408.8.4 in occupancies in Group I-3.
SEE MORE

Related Code Sections


1011.6.3 Change of Occupancy, Opening Protectives
Openings in exterior walls shall be protected as required by the International Building Code. Where openings in the exterior walls are required ...
Existing Building Code 2018 of Illinois > 10 Change of Occupancy > 1011 Change of Occupancy Classification > 1011.6 Exterior Wall Fire-Resistance Ratings > 1011.6.3 Opening Protectives
1011.7.3 Change of Occupancy, Opening Protectives
Openings in exterior walls shall be protected as required by the International Building Code. Where openings in the exterior walls are required ...
Existing Building Code 2021 of Illinois > 10 Change of Occupancy > 1011 Change of Occupancy Classification > 1011.7 Exterior Wall Fire-Resistance Ratings > 1011.7.3 Opening Protectives
1026.3 Means of Egress, Opening Protectives
Fire doors in horizontal exits shall be self-closing or automatic-closing when activated by a smoke detector in accordance with Section 716.2.6.6 ...
Building Code 2018 of Illinois > 10 Means of Egress > 1026 Horizontal Exits > 1026.3 Opening Protectives
1026.3 Means of Egress, Opening Protectives
Fire doors in horizontal exits shall be self-closing or automatic-closing when activated by a smoke detector in accordance with Section 716.2.6.6 ...
Building Code 2021 of Illinois > 10 Means of Egress > 1026 Horizontal Exits > 1026.3 Opening Protectives
3002.1.1 Elevators and Conveying Systems, Opening Protectives
Openings in hoistway enclosures shall be protected as required in Chapter 7. Exception: The elevator car doors and the associated hoistway ...
Building Code 2021 of Illinois > 30 Elevators and Conveying Systems > 3002 Hoistway Enclosures > 3002.1 Hoistway Enclosure Protection > 3002.1.1 Opening Protectives
Help Contact Us Privacy Terms
Code diagrams
Code diagrams
Unpack the code through illustrations and descriptions.
Code Compare
Code Compare
Highlight differences between any two building codes.
Code sheet exports
Code sheet exports
Generate a code sheet that integrates with your drawing set.
Code Calculators
Code Calculators
Code calculators automatically generate a detailed list of requirements.
Shared projects
Shared projects
Projects provide a dedicated space to collaborate on code research.
Search
Search
Don't miss relevant code. Quickly locate sections across your jurisdiction.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING
UpCodes Premium
Leverage the full code compliance platform.
START 2 WEEK FREE TRIAL PRICING