R303.5 Opening Location
JUMP TO FULL CODE CHAPTER
Mechanical and gravity outdoor air intake openings shall be located not less than 10 feet (3048 mm) from any hazardous or noxious contaminant, such as vents, chimneys, plumbing vents, streets, alleys, parking lots and loading docks.
For the purpose of this section, the exhaust from dwelling unit toilet rooms, bathrooms and kitchens shall not be considered as hazardous or noxious.
Exceptions:
- The 10-foot (3048 mm) separation is not required where the intake opening is located 3 feet (914 mm) or greater below the contaminant source.
- Vents and chimneys serving fuel-burning appliances shall be terminated in accordance with the applicable provisions of Chapters 18 and 24.
- Clothes dryer exhaust ducts shall be terminated in accordance with Section M1502.3.
Exhaust air shall not be directed onto walkways.
Related Code Sections
M1701.2 Combustion Air, Opening Location
In flood hazard areas as established in Table R301.2(1), combustion air openings shall be located at or above the elevation required in Section ...
R303.5 Building Planning, Opening Location
Outdoor intake and exhaust openings shall be located in accordance with Sections R303.5.1 and R303.5.2 ...
Residential Code 2018 of Kansas > 3 Building Planning > R303 Light, Ventilation and Heating > R303.5 Opening Location
304.7.2 General Regulations, Outdoor Opening Location
Outdoor opening(s) shall be located in accordance with Section 304.6 ...
Fuel Gas Code 2018 of Kansas > 3 General Regulations > 304 (IFGS) Combustion, Ventilation and Dilution Air > 304.7 Combination Indoor and Outdoor Combustion Air > 304.7.2 Outdoor Opening Location
401.4 Ventilation, Intake Opening Location
Air intake openings shall comply with all of the following: Intake openings shall be located not less than 10 feet (3048 mm) from lot lines ...
1105.6.1.1 Refrigeration, Indoor Exhaust Opening Location
Indoor mechanical exhaust intake openings shall be located where refrigerant leakage is likely to concentrate based on the refrigerant's relative ...
Mechanical Code 2018 of Kansas > 11 Refrigeration > 1105 Machinery Room, General Requirements > 1105.6 Ventilation > 1105.6.1 Discharge Location > 1105.6.1.1 Indoor Exhaust Opening Location