// CODE SNIPPET
1910.269(l)(12) Opening and Closing Circuits Under Load
JUMP TO FULL CODE CHAPTER
The employer shall ensure that devices used by employees to open circuits under load conditions are designed to interrupt the current involved.
The employer shall ensure that devices used by employees to close circuits under load conditions are designed to safely carry the current involved.
1 Employers may use the minimum approach distances in Table R-6. If the worksite is at an elevation of more than 900 meters (3,000 feet), see footnote 1 to Table R-6.
2 Employers may use the minimum approach distances in Table R-7, except that the employer may not use the minimum approach distances in Table R-7 for phase-to-phase exposures if an insulated tool spans the gap or if any large conductive object is in the gap. If the worksite is at an elevation of more than 900 meters (3,000 feet), see footnote 1 to Table R-7. Employers may use the minimum approach distances in Table 14 through Table 21 in appendix B to this section, which calculated MAD for various values of T, provided the employer follows the notes to those tables.
3 Use the equations for phase-to-ground exposures (with VPeak for phase-to-phase exposures) unless the employer can demonstrate that no insulated tool spans the gap and that no large conductive object is in the gap.
4 Until March 31, 2015, employers may use the minimum approach distances in Table 6 through Table 13 in Appendix B to this section.
1 Employers may use the minimum approach distances in this table provided the worksite is at an elevation of 900 meters (3,000 feet) or less. If employees will be working at elevations greater than 900 meters (3,000 feet) above mean sea level, the employer shall determine minimum approach distances by multiplying the distances in this table by the correction factor in Table R-5 corresponding to the altitude of the work.
2 For single-phase systems, use voltage-to-ground.
1 Employers may use the minimum approach distances in this table provided the worksite is at an elevation of 900 meters (3,000 feet) or less. If employees will be working at elevations greater than 900 meters (3,000 feet) above mean sea level, the employer shall determine minimum approach distances by multiplying the distances in this table by the correction factor in Table R-5 corresponding to the altitude of the work.
2 Employers may use the phase-to-phase minimum approach distances in this table provided that no insulated tool spans the gap and no large conductive object is in the gap.
3 The clear live-line tool distance shall equal or exceed the values for the indicated voltage ranges.
1 The distances specified in this table are for air, bare-hand, and live-line tool conditions. If employees will be working at elevations greater than 900 meters (3,000 feet) above mean sea level, the employer shall determine minimum approach distances by multiplying the distances in this table by the correction factor in Table R-5 corresponding to the altitude of the work.
For phase-to-phase system voltages of 50 V to 300 V: 1 | |
MAD = avoid contact | |
For phase-to-phase system voltages of 301 V to 5 kV: 1 | |
MAD = M + D, where | |
D = 0.02 m
|
the electrical component of the minimum approach distance. |
M = 0.31 m for voltages up to 750 V and 0.61 m otherwise
|
the inadvertent movement factor. |
For phase-to-phase system voltages of 5.1 kV to 72.5 kV:1 4 | |
MAD = M + AD, where | |
M = 0.61 m
|
the inadvertent movement factor. |
A = the applicable value from Table R-5
|
the altitude correction factor. |
D = the value from Table R-4 corresponding to the voltage and exposure or the value of the electrical component of the minimum approach distance calculated using the method provided in appendix B to this section
|
the electrical component of the minimum approach distance. |
For phase-to-phase system voltages of more than 72.5 kV, nominal:2 4 | |
MAD = 0.3048(C a)VL-G TA + M | |
C = 0.01 for phase-to-ground exposures that the employer can demonstrate consist only of air across the approach distance (gap),
|
|
0.01 for phase-to-phase exposures if the employer can demonstrate that no insulated tool spans the gap and that no large conductive object is in the gap, or
|
|
0.011 otherwise
|
|
VL-G = phase-to-ground rms voltage, in kV
|
|
T = maximum anticipated per-unit transient overvoltage; for phase-to-ground exposures, T equals TL-G, the maximum per-unit transient overvoltage, phase-to-ground, determined by the employer under paragraph (l)(3)(ii) of this section; for phase-to-phase exposures, T equals 1.35TL-G 0.45
|
|
A = altitude correction factor from Table R-5
|
|
M = 0.31 m, the inadvertent movement factor
|
|
a = saturation factor, as follows:
|
Phase-to-Ground Exposures
|
|||||
VPeak = TL-GVL-G√2 | 635 kV or less | 635.1 to 915 kV | 915.1 to 1,050 kV | More than 1,050 kV | |
a | 0 | (VPeak -635)/140,000 | (VPeak - 645)/135,000 | (VPeak - 675)/125,000 | |
Phase-to-Phase Exposures 3
|
|||||
VPeak = (1.35TL-G 0.45)VL-G√2 | 630 kV or less | 630.1 to 848 kV | 848.1 to 1,131 kV | 1,131.1 to 1,485 kV | More than 1,485 kV |
a | 0 | (VPeak - 630)/155,000 | (VPeak - 633.6)/152,207 | (VPeak - 628)/153,846 | (VPeak - 350.5)/203,666 |
1 Employers may use the minimum approach distances in Table R-6. If the worksite is at an elevation of more than 900 meters (3,000 feet), see footnote 1 to Table R-6.
2 Employers may use the minimum approach distances in Table R-7, except that the employer may not use the minimum approach distances in Table R-7 for phase-to-phase exposures if an insulated tool spans the gap or if any large conductive object is in the gap. If the worksite is at an elevation of more than 900 meters (3,000 feet), see footnote 1 to Table R-7. Employers may use the minimum approach distances in Table 14 through Table 21 in appendix B to this section, which calculated MAD for various values of T, provided the employer follows the notes to those tables.
3 Use the equations for phase-to-ground exposures (with VPeak for phase-to-phase exposures) unless the employer can demonstrate that no insulated tool spans the gap and that no large conductive object is in the gap.
4 Until March 31, 2015, employers may use the minimum approach distances in Table 6 through Table 13 in Appendix B to this section.
[D; In meters] | ||
Nominal voltage (kV)phase-to-phase | Phase-to-ground exposure | Phase-to-phase exposure |
D (m) | D (m) | |
5.1 to 15.0 | 0.04 | 0.07 |
15.1 to 36.0 | 0.16 | 0.28 |
36.1 to 46.0 | 0.23 | 0.37 |
46.1 to 72.5 | 0.39 | 0.59 |
Altitude above sea level(m) | A |
0 to 900 | 1.00 |
901 to 1,200 | 1.02 |
1,201 to 1,500 | 1.05 |
1,501 to 1,800 | 1.08 |
1,801 to 2,100 | 1.11 |
2,101 to 2,400 | 1.14 |
2,401 to 2,700 | 1.17 |
2,701 to 3,000 | 1.20 |
3,001 to 3,600 | 1.25 |
3,601 to 4,200 | 1.30 |
4,201 to 4,800 | 1.35 |
4,801 to 5,400 | 1.39 |
5,401 to 6,000 | 1.44 |
Nominal voltage (kV) phase-to-phase |
Distance | |||
Phase-to-ground exposure | Phase-to-phase exposure | |||
m | ft | m | ft | |
0.050 to 0.300 2 |
Avoid Contact
|
Avoid Contact
|
||
0.301 to 0.750 2 | 0.33 | 1.09 | 0.33 | 1.09 |
0.751 to 5.0 | 0.63 | 2.07 | 0.63 | 2.07 |
5.1 to 15.0 | 0.65 | 2.14 | 0.68 | 2.24 |
15.1 to 36.0 | 0.77 | 2.53 | 0.89 | 2.92 |
36.1 to 46.0 | 0.84 | 2.76 | 0.98 | 3.22 |
46.1 to 72.5 | 1.00 | 3.29 | 1.20 | 3.94 |
1 Employers may use the minimum approach distances in this table provided the worksite is at an elevation of 900 meters (3,000 feet) or less. If employees will be working at elevations greater than 900 meters (3,000 feet) above mean sea level, the employer shall determine minimum approach distances by multiplying the distances in this table by the correction factor in Table R-5 corresponding to the altitude of the work.
2 For single-phase systems, use voltage-to-ground.
Voltage range phase to phase (kV) | Phase-to-ground exposure | Phase-to-phase exposure | ||
m | ft | m | ft | |
72.6 to 121.0 | 1.13 | 3.71 | 1.42 | 4.66 |
121.1 to 145.0 | 1.30 | 4.27 | 1.64 | 5.38 |
145.1 to 169.0 | 1.46 | 4.79 | 1.94 | 6.36 |
169.1 to 242.0 | 2.01 | 6.59 | 3.08 | 10.10 |
242.1 to 362.0 | 3.41 | 11.19 | 5.52 | 18.11 |
362.1 to 420.0 | 4.25 | 13.94 | 6.81 | 22.34 |
420.1 to 550.0 | 5.07 | 16.63 | 8.24 | 27.03 |
550.1 to 800.0 | 6.88 | 22.57 | 11.38 | 37.34 |
1 Employers may use the minimum approach distances in this table provided the worksite is at an elevation of 900 meters (3,000 feet) or less. If employees will be working at elevations greater than 900 meters (3,000 feet) above mean sea level, the employer shall determine minimum approach distances by multiplying the distances in this table by the correction factor in Table R-5 corresponding to the altitude of the work.
2 Employers may use the phase-to-phase minimum approach distances in this table provided that no insulated tool spans the gap and no large conductive object is in the gap.
3 The clear live-line tool distance shall equal or exceed the values for the indicated voltage ranges.
Maximum anticipated per-unit transient overvoltage |
Distance (m) maximum line-to-ground voltage (kV) |
||||
250 | 400 | 500 | 600 | 750 | |
1.5 or less | 1.12 | 1.60 | 2.06 | 2.62 | 3.61 |
1.6 | 1.17 | 1.69 | 2.24 | 2.86 | 3.98 |
1.7 | 1.23 | 1.82 | 2.42 | 3.12 | 4.37 |
1.8 | 1.28 | 1.95 | 2.62 | 3.39 | 4.79 |
1 The distances specified in this table are for air, bare-hand, and live-line tool conditions. If employees will be working at elevations greater than 900 meters (3,000 feet) above mean sea level, the employer shall determine minimum approach distances by multiplying the distances in this table by the correction factor in Table R-5 corresponding to the altitude of the work.
Voltage range (kV) |
Type of current (ac or dc) |
Assumed maximum per-unit transient overvoltage |
72.6 to 420.0 | ac | 3.5 |
420.1 to 550.0 | ac | 3.0 |
550.1 to 800.0 | ac | 2.5 |
250 to 750 | dc | 1.8 |
Related Code Sections
1910.269(l)(12) Special Industries, Opening and Closing Circuits Under Load
The employer shall ensure that devices used by employees to open circuits under load conditions are designed to interrupt the current involved ...
OSHA 1910 General Industry > R Special Industries > 1910.269 Electric Power Generation, Transmission, and Distribution > 1910.269(l) Working on or Near Exposed Energized Parts > 1910.269(l)(12) Opening and Closing Circuits Under Load
1910.334(b)(1) Electrical, Routine Opening and Closing of Circuits
, or closing of circuits under load conditions. Cable connectors not of the load break type, fuses, terminal lugs, and cable splice connections may ...
OSHA 1910 General Industry > S Electrical > 1910.334 Use of Equipment > 1910.334(b) Electric Power and Lighting Circuits > 1910.334(b)(1) Routine Opening and Closing of Circuits
1910.308(a)(5) Electrical, Interrupting and Isolating Devices
only to qualified employees, open mounting of circuit breakers is permitted. A means of indicating the open and closed position of circuit breakers shall ...
OSHA 1910 General Industry > S Electrical > 1910.308 Special Systems > 1910.308(a) Systems Over 600 Volts, Nominal > 1910.308(a)(5) Interrupting and Isolating Devices
1910.308(a)(5)(vii) Electrical,
or provided with a sign warning against opening them under load ...
OSHA 1910 General Industry > S Electrical > 1910.308 Special Systems > 1910.308(a) Systems Over 600 Volts, Nominal > 1910.308(a)(5) Interrupting and Isolating Devices > 1910.308(a)(5)(vii)
1910.308(a)(5)(iv) Electrical,
the entire load. Unless the fused cutouts are interlocked with the switch to prevent opening of the cutouts under load, a conspicuous sign shall ...
OSHA 1910 General Industry > S Electrical > 1910.308 Special Systems > 1910.308(a) Systems Over 600 Volts, Nominal > 1910.308(a)(5) Interrupting and Isolating Devices > 1910.308(a)(5)(iv)