922.0 Open-Top Broiler Units
JUMP TO FULL CODE CHAPTER
Unlisted open-top broiler units shall be installed in accordance with the manufacturer's instructions but shall not be installed in combustible material. [NFPA 54:10.18.2]
Domestic open-top broiler units shall be provided with a metal ventilating hood not less than 0.0122 of an inch (0.3099 mm) thick with a clearance of not less than 1/4 of an inch (6.4 mm) between the hood and the underside of combustible material or metal cabinets. A clearance of at least 24 inches (610 mm) shall be maintained between the cooking top and the combustible material or metal cabinet, and the hood shall be at least as wide as the open-top broiler unit and centered over the unit. Listed domestic open-top broiler units incorporating an integral exhaust system and listed for use without a ventilating hood shall not be required to be provided with a ventilating hood if installed in accordance with Section 920.3.2(1). [NFPA 54:10.18.3]
Commercial open-top broiler units shall be provided with ventilation in accordance with NFPA 96. [NFPA 54:10.18.4]
Related Code Sections
922.0 Installation of Specific Appliances, Open-Top Broiler Units
Listed open-top broiler units shall be installed in accordance with the manufacturer's installation instructions. [NFPA 54:10.18.1 ...
Uniform Mechanical Code 2018 of Nevada > 9 Installation of Specific Appliances > 922.0 Open-Top Broiler Units
M1503.2.1 Exhaust Systems, Open-Top Broiler Exhaust
Domestic open-top broiler units shall be provided with a metal exhaust hood having a thickness of not less than 0.0157 inch (0.3950 mm) (No. 28 gage ...
Residential Code 2018 of Nevada > 15 Exhaust Systems > M1503 Domestic Cooking Exhaust Equipment > M1503.2 Domestic Cooking Exhaust > M1503.2.1 Open-Top Broiler Exhaust
M1901.1 Special Appliances, Equipment and Systems, Clearances
clearances for a domestic open-top broiler unit shall be in accordance with Section M1505.1 ...
Residential Code 2012 of Nevada > 19 Special Appliances, Equipment and Systems > M1901 Ranges and Ovens > M1901.1 Clearances
Section M1505 Exhaust Systems, Overhead Exhaust Hoods
Domestic open-top broiler units shall have a metal exhaust hood, having a minimum thickness of 0.0157-inch (0.3950 mm) (No. 28 gage) with 1 / 4 ...
Section M1901 Special Appliances, Equipment and Systems, Ranges and Ovens
clearances for a domestic open-top broiler unit shall be in accordance with Section M1505.1 ...
Residential Code 2012 of Nevada > 19 Special Appliances, Equipment and Systems > M1901 Ranges and Ovens