707A.4 Open Roof Eaves
JUMP TO FULL CODE CHAPTER
The exposed roof deck on the underside of unenclosed roof eaves shall consist of one of the following:
- Noncombustible material
- Ignition-resistant material
- One layer of 5/8-inch Type X gypsum sheathing applied behind an exterior covering on the underside exterior of the roof deck
- The exterior portion of a 1-hour fire resistive exterior wall assembly applied to the underside of the roof deck designed for exterior fire exposure including assemblies using the gypsum panel and sheathing products listed in the Gypsum Association Fire Resistance Design Manual
Exceptions: The following materials do not require protection:
- Solid wood rafter tails on the exposed underside of open roof eaves having a minimum nominal dimension of 2 inch (50.8 mm)
- Solid wood blocking installed between rafter tails on the exposed underside of open roof eaves having a minimum nominal dimension of 2 inch (50.8 mm)
- Gable end overhangs and roof assembly projections beyond an exterior wall other than at the lower end of the rafter tails
- Fascia and other architectural trim boards
Related Code Sections
707A.4 [SFM] Materials and Construction Methods for Exterior Wildfire Exposure, Open Roof Eaves
materials do not require protection: Solid wood rafter tails on the exposed underside of open roof eaves having a minimum nominal dimension of 2 ...
California Building Code 2016 (Vol 1 & 2) > 7A [SFM] Materials and Construction Methods for Exterior Wildfire Exposure > 707A Exterior Covering > 707A.4 Open Roof Eaves
707A.4 [SFM] Materials and Construction Methods for Exterior Wildfire Exposure, Open Roof Eaves
following materials do not require protection:
Solid wood rafter tails on the exposed underside of
open roof eaves having a minimum nominal ...
California Building Code 2019 (Vol 1 & 2) > 7A [SFM] Materials and Construction Methods for Exterior Wildfire Exposure > 707A Exterior Covering > 707A.4 Open Roof Eaves
R337.7.4 Building Planning, Open Roof Eaves
following materials do not require protection: Solid wood rafter tails on the exposed underside of open roof eaves having a minimum nominal dimension of 2 ...
California Residential Code 2016 > 3 Building Planning > R337.7 Exterior Covering > R337.7.4 Open Roof Eaves
R337.7.4 Building Planning, Open Roof Eaves
Exceptions: The following materials do not require
protection:
Solid wood rafter tails on the exposed underside
of open roof eaves having a minimum ...
California Residential Code 2019 > 3 Building Planning > R337 Materials and Construction Methods for Exterior Wildfire Exposure > R337.7 Exterior Covering > R337.7.4 Open Roof Eaves
304.3.3 General Requirements, Capacity Exceeding 1.5 Cubic Yards
or placed within 5 feet (1524 mm) of combustible walls, openings or combustible roof eave lines. Exceptions: Dumpsters or containers in areas ...
California Fire Code 2016 > 3 General Requirements > 304 Combustible Waste Material > 304.3 Containers > 304.3.3 Capacity Exceeding 1.5 Cubic Yards