601.4.1 Opaque Walls
Go To Full Code Chapter
Where the existing stud wall cavity that is part of the thermal envelope is exposed during the alteration, such exposed cavities between framing members shall be filled with insulation having a minimum nominal value of not less than R-3/inch or filled to the minimum prescriptive insulation requirement in Table R402.1.2 or Table C402.1.3 of the VECC.
Exception: Where less than 60 square feet (5.574 m2) of the existing stud cavities that are part of the thermal envelope are exposed.