602.2.2 Onsite Nonrenewable Energy
JUMP TO FULL CODE CHAPTER
Emissions associated with the use of nonrenewable energy sources other than electrical power such as natural gas, fuel oil, and propane shall be calculated by multiplying the fossil fuel energy used by the building and its site at the utility meter by the national emission factors in Table 602.2.2 and the conversions required by this section. Emissions associated with fossil fuels not specified in Table 602.2.2 shall be calculated by multiplying the fossil fuel used by the building at the utility meter by 250. Emissions associated with purchased district energy shall be calculated by multiplying the energy used by the building at the utility meter by 150 for hot water and steam, and for district cooling, the factors from Table 602.2.2 based on the EPA eGRID Sub-region in which the building is located.
TABLE 602.2.2
FOSSIL FUEL EMISSION FACTORS
FOSSIL FUEL EMISSION FACTORS
EMISSION RATE (lb/MMbtu HHV) | NATURAL GAS AS STATIONARY FUEL | FUEL OIL AS STATIONARY FUEL | PROPANE AS STATIONARY FUEL |
CO2e | 137.35 | 200.63 | 162.85 |
For SI: MMBtu = 1,000,000 Btu = 10 terms: HHV = High-heating value.
Related Code Sections
602.2.2 ENERGY CONSERVATION, EFFICIENCY AND CO2e EMISSION REDUCTION, Onsite Nonrenewable Energy
Emissions associated with the use of nonrenewable energy sources other than electrical power such as natural gas, fuel oil, and propane shall ...
Green Construction Code 2012 of Maryland > 6 ENERGY CONSERVATION, EFFICIENCY AND CO2e EMISSION REDUCTION > 602 Modeled Performance Pathway Requirements > 602.2 Annual Direct and Indirect Co2e Emissions > 602.2.2 Onsite Nonrenewable Energy
610.1.2 ENERGY CONSERVATION, EFFICIENCY AND CO2e EMISSION REDUCTION, Building Prescriptive Compliance
not less than 2 percent of the total estimated annual energy use of the building, or collective buildings on the building site, with onsite renewable ...
Green Construction Code 2012 of Maryland > 6 ENERGY CONSERVATION, EFFICIENCY AND CO2e EMISSION REDUCTION > 610 Building Renewable Energy Systems > 610.1 Renewable Energy Systems Requirements > 610.1.2 Building Prescriptive Compliance
608.12 ENERGY CONSERVATION, EFFICIENCY AND CO2e EMISSION REDUCTION, Main Electrical Panel Rating
The main electrical service entrance panel for the building shall be listed and labeled as a suitable connection to an onsite renewable energy source ...
Green Construction Code 2012 of Maryland > 6 ENERGY CONSERVATION, EFFICIENCY AND CO2e EMISSION REDUCTION > 608 Building Electrical Power and Lighting Systems > 608.12 Main Electrical Panel Rating
607.3.1 ENERGY CONSERVATION, EFFICIENCY AND CO2e EMISSION REDUCTION, Pools in Conditioned Space
or both of the following: An onsite renewable energy system. A heat recovery system ...
Green Construction Code 2012 of Maryland > 6 ENERGY CONSERVATION, EFFICIENCY AND CO2e EMISSION REDUCTION > 607 Building Service Water Heating Systems > 607.3 Pools, Hot Tubs and Spas > 607.3.1 Pools in Conditioned Space
607.3 ENERGY CONSERVATION, EFFICIENCY AND CO2e EMISSION REDUCTION, Pools, Hot Tubs and Spas
requirements for the space in which the pool is located shall be by one or both of the following: An onsite renewable energy system. A heat recovery system ...
Green Construction Code 2012 of Maryland > 6 ENERGY CONSERVATION, EFFICIENCY AND CO2e EMISSION REDUCTION > 607 Building Service Water Heating Systems > 607.3 Pools, Hot Tubs and Spas