// CODE SNIPPET
2304.10.8 Onnection Fire Resistance Rating
Go To Full Code Chapter
Wood structural connections, including connectors, fasteners, and portions of wood members included in the connection design, shall be protected from fire exposure for the required fire resistance time. For connections in Type IV construction, the required fire resistance time shall be at minimum one hour or as required for the building element by Table 601 and Section 602.4. Fire resistance ratings for connections shall be determined by one of the following:
- Testing in accordance with Section 703.2 where the connection is part of the fire resistance test.
- Engineering analysis that demonstrates that the temperature rise at any portion of the connection is limited to an average temperature rise of 250°F (139°C), and a maximum temperature rise of 325°F (181°C), for a time corresponding to the required fire resistance rating of the structural element being connected. For the purposes of this analysis, the connection includes connectors, fasteners, and portions of wood members included in the structural design of the connection.
Related Code Sections
2304.10.8 Wood, Onnection Fire Resistance Rating
one hour or as required for the building element by Table 601 and Section 602.4. Fire resistance ratings for connections shall be determined by one ...
703.2 Fire and Smoke Protection Features, Fire-Resistance Ratings
The fire-resistance rating of building elements, components or assemblies shall be determined in accordance with the test procedures set forth ...
703.2 Fire and Smoke Protection Features, Fire-Resistance Ratings
The fire-resistance rating of building elements, components or assemblies shall be determined in accordance with the test procedures set forth ...
703.2 Fire-Resistance-Rated Construction, Fire-Resistance Ratings
The fire-resistance rating of building elements shall be determined in accordance with the test procedures set forth in ASTM E 119 or in accordance ...
6.4.3 Fire Walls, Fire Resistance Rating
Where centered on a single column line, structural
framing at the column line shall have a fire resistance rating of
not less than the required fire ...