// CODE SNIPPET
1309.6.7 On-Site Recleaning
JUMP TO FULL CODE CHAPTER
The interior surfaces of tube ends, fittings, and other components that were cleaned for oxygen service by the manufacturer, but that became contaminated prior to being installed, shall be permitted to be recleaned on-site by the installer by thoroughly scrubbing the interior surfaces with a clean, hot water-alkaline solution, such as sodium carbonate or trisodium phosphate, using a solution of 1 pound (0.5 kg) of sodium carbonate or trisodium phosphate to 3 gallons (11 L) of potable water and thoroughly rinsing them with clean, hot, potable water.
Other aqueous cleaning solutions shall be permitted to be used for on-site recleaning provided that they are as recommended in the mandatory requirements of CGA G-4.1. [NFPA 99:5.1.10.4.3.10, 5.1.10.4.3.11]
Related Code Sections
1309.6.7 Health Care Facilities and Medical Gas and Medical Vacuum Systems, On-Site Recleaning
contaminated prior to being installed, shall be permitted to be recleaned on-site by the installer by thoroughly scrubbing the interior surfaces with a clean ...
Uniform Plumbing Code 2018 of Nevada > 13 Health Care Facilities and Medical Gas and Medical Vacuum Systems > 1309.0 Joints and Connections > 1309.6 Cleaning Procedures > 1309.6.7 On-Site Recleaning
2.4-4.1.1.2 Specific Requirements for Critical Access Hospitals, On-Site Facilities
Where laboratory services are provided on contract, the support spaces included in this section (2.4-4.1, Laboratory Services) shall be provided ...
Guidelines for Design and Construction of Hospitals 2018 of Nevada > 2.4 Specific Requirements for Critical Access Hospitals > 2.4-4 Patient Support Facilities > 2.4-4.1 Laboratory Services > 2.4-4.1.1 General > 2.4-4.1.1.2 On-Site Facilities
R506.2 Floors, Site Preparation
site conditions. Where provided in slabs ...
Residential Code 2018 of Nevada > 5 Floors > R506 Concrete Floors (On Ground) > R506.2 Site Preparation
R506.2 Floors, Site Preparation
not likely to be enclosed and heated at a later date. Where approved by the building official , based on local site conditions ...
Residential Code 2012 of Nevada > 5 Floors > R506 Concrete Floors (On Ground) > R506.2 Site Preparation
R504.2 Floors, Site Preparation
The area within the foundation walls shall have all vegetation, topsoil and foreign material removed, and any fill material that is added shall ...
Residential Code 2018 of Nevada > 5 Floors > R504 Pressure Preservative-Treated Wood Floors (On Ground) > R504.2 Site Preparation