3110F.6 Oil Sumps and Ancillary Equipment
JUMP TO FULL CODE CHAPTER
Oil sumps and ancillary equipment shall conform to the following:
- Sumps for oil drainage shall be equipped with pressure/vacuum vents, automatic draining pumps and shall be tightly covered (N/E).
- Sumps which provide drainage for more than one berth should be equipped with liquid seals so that a fire on one berth does not spread via the sump (N/E).
- Sumps shall be located at least 25ft from the manifolds, base of the loading arms or hose towers (N).
- Conduct periodic integrity testing of the sump containers and periodic integrity and leak testing of the related valves and piping.
Related Code Sections
3110F.6 [SLC] Marine Oil Terminals, Oil Sumps and Ancillary Equipment
Oil sumps and ancillary equipment shall conform to the following: Sumps for oil drainage shall be equipped with pressure/vacuum vents, automatic ...
California Building Code 2016 (Vol 1 & 2) > 31F [SLC] Marine Oil Terminals > 3110F Mechanical and Electrical Equipment > 3110F.6 Oil Sumps and Ancillary Equipment
3110F.6 [SLC] Marine Oil Terminals, Oil Sumps and Ancillary Equipment
Oil sumps
and ancillary equipment shall conform to the following:
Sumps for oil drainage shall be equipped with
pressure/vacuum vents ...
California Building Code 2019 (Vol 1 & 2) > 31F [SLC] Marine Oil Terminals > 3110F Mechanical and Electrical Equipment > 3110F.6 Oil Sumps and Ancillary Equipment
Section 3110F [SLC] Marine Oil Terminals, Mechanical and Electrical Equipment
/E).
Oil sumps
and ancillary equipment ...
California Building Code 2019 (Vol 1 & 2) > 31F [SLC] Marine Oil Terminals > 3110F Mechanical and Electrical Equipment
5706.3.3 Flammable and Combustible Liquids, Sumps
Sumps or other basins for the retention of oil or petroleum products shall not exceed 12 feet (3658 mm) in width ...
California Fire Code 2016 > 57 Flammable and Combustible Liquids > 5706 Special Operations > 5706.3 Well Drilling and Operating > 5706.3.3 Sumps
5706.3.3 Flammable and Combustible Liquids, Sumps
Sumps or other basins for the retention of oil or petroleum products shall not exceed 12 feet (3658 mm) in width ...
California Fire Code 2019 > 57 Flammable and Combustible Liquids > 5706 Special Operations > 5706.3 Well Drilling and Operating > 5706.3.3 Sumps