At repair garages where floor or trench drains are provided, car washing facilities, factories where oily and flammable liquid wastes are produced and hydraulic elevator pits, oil separators shall be installed into which oil-bearing, grease-bearing or flammable wastes shall be discharged before emptying into the building drainage system or other point of disposal.
Exception: An oil separator is not required in hydraulic elevator pits where an approved alarm system is installed. Such alarm systems shall not terminate the operation of pumps utilized to maintain emergency operation of the elevator by fire fighters.
1003.4.1 Separation of Liquids
A mixture of treated or untreated light and heavy liquids with various specific gravities shall be separated in an approved receptacle.
1003.4.2 Oil Separator Design
Oil separators shall be listed and labeled, or designed in accordance with Sections 1003.4.2.1 and 1003.4.2.2.
1003.4.2.1 General Design Requirements
Oil separators shall have a depth of not less than 2 feet (610 mm) below the invert of the discharge drain. The outlet opening of the separator shall have not less than an 18-inch (457 mm) water seal.
1003.4.2.2 Garages and Service Stations
Where automobiles are serviced, greased, repaired or washed or where gasoline is dispensed, oil separators shall have a capacity of not less than 6 cubic feet (0.168 m3) for the first 100 square feet (9.3 m2) of area to be drained, plus 1 cubic foot (0.028 m3) for each additional 100 square feet (9.3 m2) of area to be drained into the separator. Parking garages in which servicing, repairing or washing is not conducted, and in which gasoline is not dispensed, shall not require a separator. Areas of commercial garages utilized only for storage of automobiles are not required to be drained through a separator.

Related Code Sections

1003.4 Traps, Interceptors and Separators, Oil Separators Required
emptying into the building drainage system or other point of disposal. Exception: An oil separator is not required in hydraulic elevator pits where ...
1003.4 Traps, Interceptors and Separators, Oil Separators Required
emptying into the building drainage system or other point of disposal. Exception: An oil separator is not required in hydraulic elevator pits where ...
1003.4 Traps, Interceptors and Separators, Oil Separators Required
system or other point of disposal. Exception: An oil separator is not required in hydraulic elevator pits where an approved alarm system is installed ...