1306.1 Level Indication
Tanks in which a constant oil level is not maintained by an automatic pump shall be equipped with a method of determining the oil level.
1306.2 Test Wells
Test wells shall not be installed inside buildings. For outdoor service, test wells shall be equipped with a tight metal cover designed to discourage tampering.
1306.3 Inside Tanks
The gauging of inside tanks by means of measuring sticks shall not be permitted. An inside tank provided with fill and vent pipes shall be provided with a device to indicate either visually or audibly at the fill point when the oil in the tank has reached a predetermined safe level.
1306.4 Gauging Devices
Gauging devices such as liquid level indicators or signals shall be designed and installed so that oil vapor will not be discharged into a building from the liquid fuel supply system. Liquid-level indicating gauges shall comply with UL 180.
1306.5 Gauge Glass
A tank used in connection with any oil burner shall not be equipped with a glass gauge or any gauge that, when broken, will permit the escape of oil from the tank.

Related Code Sections

Section 1306 Fuel Oil Piping and Storage, Oil Gauging
A tank used in connection with any oil burner shall not be equipped with a glass gauge or any gauge that, when broken, will permit ...
Section 1306 Fuel Oil Piping and Storage, Oil Gauging
A tank used in connection with any oil burner shall not be equipped with a glass gauge or any gauge that, when broken, will permit ...
Section 1306 Fuel Oil Piping and Storage, Oil Gauging
A tank used in connection with any oil burner shall not be equipped with a glass gauge or any gauge which, when broken ...
M2201.5 Special Piping and Storage Systems, Oil Gauges
Inside tanks shall be provided with a device to indicate when the oil in the tank has reached a predetermined safe level. Glass gauges or a gauge ...