1207.4.10 Occupied Work Centers
JUMP TO FULL CODE CHAPTER
Electrochemical ESS located in rooms or areas occupied by personnel not directly involved with maintenance, service and testing of the systems shall comply with the following:
- Electrochemical ESS located in occupied work centers shall be housed in locked noncombustible cabinets or other enclosures to prevent access by unauthorized personnel.
- Where electrochemical ESS are contained in cabinets in occupied work centers, the cabinets shall be located within 10 feet (3048 mm) of the equipment that they support.
- Cabinets shall include signage complying with Section 1207.4.8.
Related Code Sections
1206.2.8.5 Energy Systems, Occupied Work Centers
Where stationary storage batteries are located in an occupied work center, they shall be housed in a noncombustible cabinet or other enclosure ...
Fire Code 2018 of Colorado > 12 Energy Systems > 1206 Electrical Energy Storage Systems > 1206.2 Stationary Storage Battery Systems > 1206.2.8 Location and Construction > 1206.2.8.5 Occupied Work Centers
1207.4.10 Energy Systems, Occupied Work Centers
comply with the following: Electrochemical ESS located in occupied work centers shall be housed in locked noncombustible cabinets or other ...
Fire Code 2021 of Colorado > 12 Energy Systems > 1207 Electrical Energy Storage Systems (ESS) > 1207.4 General Installations Requirements > 1207.4.10 Occupied Work Centers
1207.1.4.2 Energy Systems, Analysis Approval
identified in Section 1207.7.4. Fires in occupied work centers will be detected in time to allow occupants within the room or area to safely evacuate. Toxic ...
Fire Code 2021 of Colorado > 12 Energy Systems > 1207 Electrical Energy Storage Systems (ESS) > 1207.1 General > 1207.1.4 Hazard Mitigation Analysis > 1207.1.4.2 Analysis Approval
1206.2.3.2 Energy Systems, Analysis Approval
walls identified in Table 509.1 of the International Building Code . Fires and explosions in battery cabinets in occupied work centers ...
Fire Code 2018 of Colorado > 12 Energy Systems > 1206 Electrical Energy Storage Systems > 1206.2 Stationary Storage Battery Systems > 1206.2.3 Hazard Mitigation Analysis > 1206.2.3.2 Analysis Approval
1206.2.8.6 Energy Systems, Signage
Battery storage cabinets provided in occupied work centers in accordance with Section 1206.2.8.5 shall have exterior labels that identify ...
Fire Code 2018 of Colorado > 12 Energy Systems > 1206 Electrical Energy Storage Systems > 1206.2 Stationary Storage Battery Systems > 1206.2.8 Location and Construction > 1206.2.8.6 Signage