402.4.1.2.1 Occupant Load Formula
JUMP TO FULL CODE CHAPTER
To determine the occupant load attributed to the mall, the gross leasable area (square feet), excluding any food court and anchor buildings, shall be divided by the occupant load factor (OLF) value determined by Equation 4-1.
where:
Exception: Tenant spaces attached to a covered mall building but with a means of egress system that is totally independent of the covered mall building shall not be considered as gross leasable area for determining the required means of egress for the covered mall building.

where:
OLF | = | The occupant load factor (square feet per person). |
GLA | = | The gross leasable area (square feet). |
Exception: Tenant spaces attached to a covered mall building but with a means of egress system that is totally independent of the covered mall building shall not be considered as gross leasable area for determining the required means of egress for the covered mall building.
Related Code Sections
402.4.1.2.1 Special Detailed Requirements Based on Use and Occupancy, Occupant Load Formula
To determine the occupant load attributed to the mall, the gross leasable area (square feet), excluding any food court and anchor buildings, shall ...
NYC Building Code 2014 > 4 Special Detailed Requirements Based on Use and Occupancy > 402 Covered Mall and Open Mall Buildings > 402.4 Means of Egress > 402.4.1 Occupant Load > 402.4.1.2 Occupant Load of Mall > 402.4.1.2.1 Occupant Load Formula
402.4.1.2.1 Special Detailed Requirements Based on Use and Occupancy, Occupant Load Formula
To determine the occupant load attributed to the mall, the number of square feet of floor area of the mall, excluding any food court, shall ...
NYC Building Code 2008 > 4 Special Detailed Requirements Based on Use and Occupancy > 402 Covered Mall Buildings > 402.4 Means of Egress > 402.4.1 Occupant Load > 402.4.1.2 Occupant Load of Mall > 402.4.1.2.1 Occupant Load Formula
402.8.2.3 Special Detailed Requirements Based on Use and Occupancy, Occupant Load Formula
To determine the occupant load attributed to the mall, the
gross leasable area (square feet), excluding any food court and anchor buildings, shall ...
NYC Building Code 2022 > 4 Special Detailed Requirements Based on Use and Occupancy > 402 Covered Mall and Open Mall Buildings > 402.8 Means of Egress > 402.8.2 Occupant Load > 402.8.2.3 Occupant Load Formula
2409.4 Glass and Glazing, Design Formula
, and F ga is the maximum allowable load on the glass, computed by the following formula:
F ga = 0.67 c 2 F ge
(Equation 24-15 ...
NYC Building Code 2008 > 24 Glass and Glazing > 2409 Glass in Floors and Sidewalks > 2409.4 Design Formula
8.2.2.1.1 General Requirements, Formula Symbols
The symbols used in the formulas in 8.2.2 shall have the following meaning: A = net area of section, m 2 (in. 2 ) B ...
Safety Code for Elevators and Escalators 2013 of New York City > 8 General Requirements > 8.2 Design Data and Formulas > 8.2.2 Electric Elevator Car Frame and Platform Stresses and Deflections > 8.2.2.1 General Requirements > 8.2.2.1.1 Formula Symbols