2702.2.20 Occupancy Groups B, E and R-1
JUMP TO FULL CODE CHAPTER
Emergency and standby power shall be required throughout those Group B, E and R-1 occupancies specified throughout this section:
- Group B occupancies with occupied floor less than 75 feet (22 860 mm) above the lowest level of fire department vehicle access having a gross floor area over 15,000 square feet (1393.6 m2) on each floor, or having a total gross floor area of 100,000 square feet (9290.3 m2 ) or more.
- Group E occupancies with occupied floor less than 75 feet (22 860 mm) above the lowest level of fire department vehicle access having a gross floor area over 15,000 square feet (1393.6 m2) on each floor, or having a total gross floor area of 100,000 square feet (9290.3 m2) or more.
- All Group R-1 occupancies.
With respect to such Occupancy Groups B, E and R-1, the following equipment, where such equipment is required by this code, shall be provided with an emergency power system:
- Exit signs and means of egress illumination required by Chapter 10;
- Elevator car lighting;
- Emergency voice/alarm communications systems, including Fire Department in-building Auxiliary Radio Communication systems (ARCs) provided where required or installed voluntarily in accordance with Section 916;
- Automatic fire detection systems;
- Fire alarm systems; and
- Electrically powered fire pumps, including manual fire pumps, automatic fire pumps and sprinkler booster pumps.
With respect to such Occupancy Groups B, E and R-1, the following equipment, where such equipment is required by this code, shall be provided with a standby power system:
- Ventilating systems used for smoke venting or control;
- Stair pressurization;
- At least three elevators in a building at one time with manual transfer to other elevators as required by Section 3003; and
- Power and lighting for the fire command center required by Section 403.4.6.
Related Code Sections
2702.2.20 Electrical, Occupancy Groups B, E and R-1
Emergency and standby power shall be required throughout those Group B, E and R-1 occupancies specified throughout this section:
Group B ...
NYC Building Code 2022 > 27 Electrical > 2702 Emergency and Standby Power Systems > 2702.2 Where Required > 2702.2.20 Occupancy Groups B, E and R-1
2702.2.20 Electrical, Occupancy Groups B, E and R-1
Emergency and standby power shall be required in those Group B, E and R-1 occupancies specified in this section: Group B occupancies with occupied ...
NYC Building Code 2014 > 27 Electrical > 2702 Emergency and Standby Power Systems > 2702.2 Where Required > 2702.2.20 Occupancy Groups B, E and R-1
2702.2.20 Electrical, Occupancy Groups B, E and R-1
Emergency and standby power shall be required in those Group B, E and R-1 occupancies specified in this section: Group B occupancies with occupied ...
NYC Building Code 2008 > 27 Electrical > 2702 Emergency and Standby Power Systems > 2702.2 Where Required > 2702.2.20 Occupancy Groups B, E and R-1
2702.2.20.1 Electrical, Equipment Requiring Emergency Power System
With respect to such Occupancy Groups B, E and R-1, the following equipment, where such equipment is required by this code, shall be provided ...
NYC Building Code 2014 > 27 Electrical > 2702 Emergency and Standby Power Systems > 2702.2 Where Required > 2702.2.20 Occupancy Groups B, E and R-1 > 2702.2.20.1 Equipment Requiring Emergency Power System
2702.2 Electrical, Where Required
, E and R-1 occupancies specified in this section: Group B occupancies with occupied floor less than 75 feet (22 860 mm) above the lowest fire ...
NYC Building Code 2014 > 27 Electrical > 2702 Emergency and Standby Power Systems > 2702.2 Where Required