P2904.2.4.2 Obstructions to Coverage
JUMP TO FULL CODE CHAPTER
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
Sprinkler discharge shall not be blocked by obstructions unless additional sprinklers are installed to protect the obstructed area. Additional sprinklers shall not be required where the sprinkler separation from obstructions complies with either the minimum distance indicated in Figure P2904.2.4.2 or the minimum distances specified in the sprinkler manufacturer's instructions where the manufacturer's instructions permit a lesser distance.

MINIMUM ALLOWABLE DISTANCE BETWEEN SPRINKLER AND OBSTRUCTION
Pendent sprinklers within 3 feet (915 mm) of the center of a ceiling fan, surface-mounted ceiling luminaire or similar object shall be considered to be obstructed, and additional sprinklers shall be installed.
Sidewall sprinklers within 5 feet (1524 mm) of the center of a ceiling fan, surface-mounted ceiling luminaire or similar object shall be considered to be obstructed, and additional sprinklers shall be installed.
Related Code Sections
P2904.2.4.2 Water Supply and Distribution, Obstructions to Coverage
Sprinkler discharge shall not be blocked by obstructions unless additional sprinklers are installed to protect the obstructed area. Additional ...
Residential Code 2018 of Kansas > 29 Water Supply and Distribution > P2904 Dwelling Unit Fire Sprinkler Systems > P2904.2 Sprinklers > P2904.2.4 Sprinkler Coverage > P2904.2.4.2 Obstructions to Coverage
8.9.5.1.3 Installation Requirements,
8.9.5.1.3 and Figure 8.9.5.1.3. Table 8.9.5.1.3 Positioning of Sprinklers to Avoid Obstructions (Extended Coverage Sidewall Spray Sprinklers ...
Standard for the Installation of Sprinkler Systems 2016 of Kansas > 8 Installation Requirements > 8.9* Extended Coverage Sidewall Spray Sprinklers > 8.9.5 Obstructions to Sprinkler Discharge (Extended Coverage Sidewall Spray Sprinklers) > 8.9.5.1 Performance Objective > 8.9.5.1.3
8.8.5.2.2 Installation Requirements, Suspended or Floor-Mounted Vertical Obstructions
be in accordance with Table 8.8.5.2.2 and Figure 8.8.5.2.2. Table 8.8.5.2.2 Suspended or Floor-Mounted Obstructions (Extended Coverage Upright ...
Standard for the Installation of Sprinkler Systems 2016 of Kansas > 8 Installation Requirements > 8.8 Extended Coverage Upright and Pendent Spray Sprinklers > 8.8.5 Obstructions to Sprinkler Discharge (Extended Coverage Upright and Pendent Spray Sprinklers) > 8.8.5.2 Obstructions to Sprinkler Discharge Pattern Development > 8.8.5.2.2 Suspended or Floor-Mounted Vertical Obstructions
8.9.5.2 Installation Requirements, Obstructions to Sprinkler Discharge Pattern Development
is greater) FIGURE 8.9.5.2.1.3(a) Minimum Distance from an Obstruction in the Vertical Orientation (Extended Coverage Sidewall). A ≥ 4 C or 4 ...
Standard for the Installation of Sprinkler Systems 2016 of Kansas > 8 Installation Requirements > 8.9* Extended Coverage Sidewall Spray Sprinklers > 8.9.5 Obstructions to Sprinkler Discharge (Extended Coverage Sidewall Spray Sprinklers) > 8.9.5.2 Obstructions to Sprinkler Discharge Pattern Development
21.5.2.2 Alternative Sprinkler System Designs for Chapters 12 Through 20,
Control mode density/area (CMDA) and CMSA sprinklers having standard coverage areas requiring more than 20 sprinklers in the design area shall ...
Standard for the Installation of Sprinkler Systems 2016 of Kansas > 21 Alternative Sprinkler System Designs for Chapters 12 Through 20 > 21.5 Minimum Obstruction Criteria > 21.5.2 Standard Coverage Spacing Sprinklers > 21.5.2.2