1224.33.5.1 Observation Units
JUMP TO FULL CODE CHAPTER
Observation rooms for the monitoring of patients up to 24 hours may be provided as a distinct unit within, the emergency department. If provided the unit shall have the following:
- Handwashing stations shall be provided in each patient room and for each four treatment stations, and for each major fraction thereof. These shall be uniformly distributed to provide equal access from each patient station. Handwashing stations shall be directly accessible to nurse stations and patient care areas.
- Each patient station shall have a minimum of 120 square feet (11.15 m2) of clear floor area including space at each bedside for visitors and provision for visual privacy from casual observation by other patients and visitors.
- One toilet room shall be provided for each six treatment stations and for each major fraction thereof.
- An administrative center/nurse station, in compliance with Section 1224.4.4.2, positioned to allow staff to observe each patient care station or room.
- A nourishment area in compliance with Section 1224.4.4.5.
Related Code Sections
1224.33.5.1 Interior Environment, Observation Units
Observation rooms for the monitoring of patients up to 24 hours may be provided as a distinct unit within, the emergency department. If provided ...
California Building Code 2016 (Vol 1 & 2) > 12 Interior Environment > 1224 [OSHPD 1] Hospitals > 1224.33 Emergency Service > 1224.33.5 Other Space Considerations > 1224.33.5.1 Observation Units
1224.33.5.1 Interior Environment, Observation Units
Observation rooms for
the monitoring of patients up to 24 hours may be provided
as a distinct unit within, the emergency department.
If provided ...
California Building Code 2019 (Vol 1 & 2) > 12 Interior Environment > 1224 [OSHPD 1] Hospitals > 1224.33 Emergency Service > 1224.33.5 Other Space Considerations > 1224.33.5.1 Observation Units
1224.39.6 Interior Environment, Outpatient Observation Units
If provided, outpatient observation
unit(s) shall comply with the following ...
California Building Code 2019 (Vol 1 & 2) > 12 Interior Environment > 1224 [OSHPD 1] Hospitals > 1224.39 Outpatient Service Space > 1224.39.6 Outpatient Observation Units
1224.39.6.1 Interior Environment, General
If provided, outpatient observation
unit(s) shall comply with the following: ...
California Building Code 2019 (Vol 1 & 2) > 12 Interior Environment > 1224 [OSHPD 1] Hospitals > 1224.39 Outpatient Service Space > 1224.39.6 Outpatient Observation Units > 1224.39.6.1 General
1224.39.6.5 Interior Environment, Service Areas
Unless otherwise indicated,
provisions for the services listed below shall be in or
immediately accessible to each outpatient observation
unit ...
California Building Code 2019 (Vol 1 & 2) > 12 Interior Environment > 1224 [OSHPD 1] Hospitals > 1224.39 Outpatient Service Space > 1224.39.6 Outpatient Observation Units > 1224.39.6.5 Service Areas