1224.33.2.7 Observation Area
JUMP TO FULL CODE CHAPTER
A patient cubicle with a
minimum clear floor area of 100 square feet (9.29 m2)
shall be provided under the visual control of an emergency
service staff work area. The patient station shall
have space at bedside for visitors and shall have provision
for visual privacy from casual observation by
other patients and visitors. A handwashing station shall
be located in each room, and at least one handwashing
station shall be provided for every four patient stations, and for each major fraction thereof, in open-bay areas.
These shall be uniformly distributed to provide equal
access from each patient station.
Related Code Sections
1224.33.2.7 Interior Environment, Observation Area
staff work area. The patient station shall
have space at bedside for visitors and shall have provision
for visual privacy from casual observation ...
California Building Code 2016 (Vol 1 & 2) > 12 Interior Environment > 1224 [OSHPD 1] Hospitals > 1224.33 Emergency Service > 1224.33.2 Standby Emergency Medical Service > 1224.33.2.7 Observation Area
1224.33.2.7 Interior Environment, Observation Area
staff work area. The patient station shall
have space at bedside for visitors and shall have provision
for visual privacy from casual observation ...
California Building Code 2019 (Vol 1 & 2) > 12 Interior Environment > 1224 [OSHPD 1] Hospitals > 1224.33 Emergency Service > 1224.33.2 Standby Emergency Medical Service > 1224.33.2.7 Observation Area
1224.33.3.3 Interior Environment, Reception, Triage, and Control Station(s)
This area shall be located to permit staff observation
and control of access to treatment areas, pedestrian
and ambulance entrances, and public ...
California Building Code 2019 (Vol 1 & 2) > 12 Interior Environment > 1224 [OSHPD 1] Hospitals > 1224.33 Emergency Service > 1224.33.3 Basic Emergency Medical Service > 1224.33.3.3 Reception, Triage, and Control Station(s)
1224.39.6.5.7 Interior Environment, Nourishment Area
A nourishment
area, in compliance with Section 1224.4.4.5, shall
be provided within the unit ...
California Building Code 2019 (Vol 1 & 2) > 12 Interior Environment > 1224 [OSHPD 1] Hospitals > 1224.39 Outpatient Service Space > 1224.39.6 Outpatient Observation Units > 1224.39.6.5 Service Areas > 1224.39.6.5.7 Nourishment Area
1224.39.6.5.15 Interior Environment, Portable Oxygen Storage
for fire separations.
Portable oxygen storage may be omitted if
station outlets per Table 1224.4.6.1 "observation
unit" footnote 8 are provided ...
California Building Code 2019 (Vol 1 & 2) > 12 Interior Environment > 1224 [OSHPD 1] Hospitals > 1224.39 Outpatient Service Space > 1224.39.6 Outpatient Observation Units > 1224.39.6.5 Service Areas > 1224.39.6.5.15 Portable Oxygen Storage