407.2.5 Nursing Home Housing Units
JUMP TO FULL CODE CHAPTER
In Group I-2, Condition 1 occupancies, in areas where nursing home residents are housed, shared living spaces, group meeting or multipurpose therapeutic spaces shall be permitted to be open to the corridor, where all of the following criteria are met:
- The walls and ceilings of the space are constructed as required for corridors.
- The spaces are not occupied as resident sleeping rooms, treatment rooms, incidental uses in accordance with Section 509, or hazardous uses.
- The open space is protected by an automatic fire detection system installed in accordance with Section 907.
- The corridors onto which the spaces open, in the same smoke compartment, are protected by an automatic fire detection system installed in accordance with Section 907, or the smoke compartment in which the spaces are located is equipped throughout with quick-response sprinklers in accordance with Section 903.3.2.
- The space is arranged so as not to obstruct access to the required exits.
Related Code Sections
407.2.5 Special Detailed Requirements Based on Occupancy and Use, Nursing Home Housing Units
In Group I-2, Condition 1 occupancies, in areas where nursing home residents are housed, shared living spaces, group meeting or multipurpose ...
Building Code 2021 of Illinois > 4 Special Detailed Requirements Based on Occupancy and Use > 407 Group I-2 > 407.2 Corridors Continuity and Separation > 407.2.5 Nursing Home Housing Units
407.2.5 Special Detailed Requirements Based on Occupancy and Use, Nursing Home Housing Units
In Group I-2, Condition 1 occupancies, in areas where nursing home residents are housed, shared living spaces, group meeting or multipurpose ...
Building Code 2018 of Illinois > 4 Special Detailed Requirements Based on Occupancy and Use > 407 Group I-2 > 407.2 Corridors Continuity and Separation > 407.2.5 Nursing Home Housing Units
1107.5.2 Accessibility, Group I-2 Nursing Homes
Accessible units and Type B units shall be provided in nursing homes of Group I-2 occupancies in accordance with Sections 1107.5.2.1 ...
Building Code 2018 of Illinois > 11 Accessibility > 1107 Dwelling Units and Sleeping Units > 1107.5 Group I > 1107.5.2 Group I-2 Nursing Homes
1108.5.2 Accessibility, Group I-2 Nursing Homes
Accessible units and Type B units shall be provided in nursing homes of Group I-2, Condition 1 occupancies in accordance with Sections ...
Building Code 2021 of Illinois > 11 Accessibility > 1108 Dwelling Units and Sleeping Units > 1108.5 Group I > 1108.5.2 Group I-2 Nursing Homes
704.1.1 Alterations—Level 1, Projections in Nursing Home Corridors
In Group I-2, Condition 1 occupancies, where the corridor is at least 96 inches (2438 mm) wide, projections into the corridor width are permitted ...
Existing Building Code 2021 of Illinois > 7 Alterations—Level 1 > 704 Means of Egress > 704.1 General > 704.1.1 Projections in Nursing Home Corridors