G2414.9.2 (403.9.2) Number of Threads
JUMP TO FULL CODE CHAPTER
Field threading of metallic pipe shall be in accordance with Table G2414.9.2.
TABLE G2414.9.2 (403.9.2)
SPECIFICATIONS FOR THREADING METALLIC PIPE
IRON PIPE SIZE (inches) | APPROXIMATE LENGTH OF THREADED PORTION (inches) | APPROXIMATE NO. OF THREADS TO BE CUT |
1/2 | 3/4 | 10 |
3/4 | 3/4 | 10 |
1 | 7/8 | 10 |
11/4 | 1 | 11 |
11/2 | 1 | 11 |
For SI: 1 inch = 25.4 mm.
Related Code Sections
G2414.9.2 Fuel Gas, (403.9.2) Number of Threads
Field threading of metallic pipe shall be in accordance with Table G2414.9.2. TABLE G2414.9.2 (403.9.2) SPECIFICATIONS FOR THREADING METALLIC ...
Residential Code 2018 of Kansas > 24 Fuel Gas > G2414 (403) Piping Materials > G2414.9 (403.9) Metallic Pipe Threads > G2414.9.2 (403.9.2) Number of Threads
403.9.2 Gas Piping Installations, Number of Threads
Field threading of metallic pipe shall be in accordance with Table 403.9.2. TABLE 403.9.2 SPECIFICATIONS FOR THREADING METALLIC PIPE IRON ...
Fuel Gas Code 2018 of Kansas > 4 Gas Piping Installations > 403 (IFGS) Piping Materials > 403.9 Metallic Pipe Threads > 403.9.2 Number of Threads
3.19.2.2 Hydraulic Elevators, Threading
Pipe lighter than Schedule 40 shall not be threaded ...
Safety Code for Elevators and Escalators 2016 of Kansas > 3 Hydraulic Elevators > 3.19 Valves, Pressure Piping, and Fittings > 3.19.2 Pressure Piping > 3.19.2.2 Threading
(B) Wiring Methods and Materials, Threading
EMT shall not be threaded. Exception: EMT with factory threaded integral couplings complying with 358.100 ...
National Electrical Code 2017 of Kansas > 3 Wiring Methods and Materials > 358 Electrical Metallic Tubing: Type EMT > 358.28 Reaming and Threading > (B) Threading
(E) Special Occupancies, Threading
The supply connection entry thread form shall be NPT or metric. Conduit and fittings shall be made wrenchtight to prevent sparking when fault current ...
National Electrical Code 2017 of Kansas > 5 Special Occupancies > 500 Hazardous (Classified) Locations, Classes I, II, and III, Divisions 1 and 2 > 500.8 Equipment > (E) Threading