504.4 Number of Stories

Building Code 2015 of Utah > 5 General Building Heights and Areas > 504 Building Height and Number of Stories > 504.4 Number of Stories
JUMP TO FULL CODE CHAPTER
Share URL

Copy and paste the link below into emails, chats or browsers.


You can also copy or bookmark the link from your browser's address bar.
The maximum number of stories of a building shall not exceed the limits specified in Table 504.4.

TABLE 504.4a, b ALLOWABLE NUMBER OF STORIES ABOVE GRADE PLANE

OCCUPANCY CLASSIFICATION TYPE OF CONSTRUCTION
SEE FOOTNOTES TYPE I TYPE II TYPE III TYPE IV TYPE V
A B A B A B HT A B
A-1 NS UL 5 3 2 3 2 3 2 1
S UL 6 4 3 4 3 4 3 2
A-2 NS UL 11 3 2 3 2 3 2 1
S UL 12 4 3 4 3 4 3 2
A-3 NS UL 11 3 2 3 2 3 2 1
S UL 12 4 3 4 3 4 3 2
A-4 NS UL 11 3 2 3 2 3 2 1
S UL 12 4 3 4 3 4 3 2
A-5 NS UL UL UL UL UL UL UL UL UL
S UL UL UL UL UL UL UL UL UL
B NS UL 11 5 3 5 3 5 3 2
S UL 12 6 4 6 4 6 4 3
E NS UL 5 3 2 3 2 3 1 1
S UL 6 4 3 4 3 4 2 2
F-1 NS UL 11 4 2 3 2 4 2 1
S UL 12 5 3 4 3 5 3 2
F-2 NS UL 11 5 3 4 3 5 3 2
S UL 12 6 4 5 4 6 4 3
H-1 NSc, d 1 1 1 1 1 1 1 1 NP
S
H-2 NSc, d UL 3 2 1 2 1 2 1 1
S
H-3 NSc, d UL 6 4 2 4 2 4 2 1
S
H-4 NSc, d UL 7 5 3 5 3 5 3 2
S UL 8 6 4 6 4 6 4 3
H-5 NSc, d 4 4 3 3 3 3 3 3 2
S
I-1 Condition 1 NSd, e UL 9 4 3 4 3 4 3 2
S UL 10 5 4 5 4 5 4 3
I-1 Condition 2 NSd, e UL 9 4 3 4 3 4 3 2
S UL 10 5
I-2 NSd, f UL 4 2 1 1 NP 1 1 NP
S UL 5 3
I-3 NSd, e UL 4 2 1 2 1 2 2 1
S UL 5 3 2 3 2 3 3 2
I-4 NSd, g UL 5 3 2 3 2 3 1 1
S UL 6 4 3 4 3 4 2 2
M NS UL 11 4 2 4 2 4 3 1
S UL 12 5 3 5 3 5 4 2

(continued)

TABLE 504.4a, b‒continued ALLOWABLE NUMBER OF STORIES ABOVE GRADE PLANE

OCCUPANCY CLASSIFICATION TYPE OF CONSTRUCTION
SEE FOOTNOTES TYPE I TYPE II TYPE III TYPE IV TYPE V
A B A B A B HT A B
R-1 NSd, h UL 11 4 4 4 4 4 3 2
S13R 4 4 4 3
S UL 12 5 5 5 5 5 4 3
R-2 NSd, h UL 11 4 4 4 4 4 3 2
S13R 4 4 4 4 3
S UL 12 5 5 5 5 5 4 3
R-3 NSd, h UL 11 4 4 4 4 4 3 3
S13R 4 4 4 4
S UL 12 5 5 5 5 5 4 4
R-4 NSd, h UL 11 4 4 4 4 4 3 2
S13R 4 4 4 3
S UL 12 5 5 5 5 5 4 3
S-1 NS UL 11 4 2 3 2 4 3 1
S UL 12 5 3 4 3 5 4 2
S-2 NS UL 11 5 3 4 3 4 4 2
S UL 12 6 4 5 4 5 5 3
U NS UL 5 4 2 3 2 4 2 1
S UL 6 5 3 4 3 5 3 2

Note: UL = Unlimited; NP = Not Permitted; NS = Buildings not equipped throughout with an automatic sprinkler system; S = Buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1; S13R = Buildings equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.2.
a. See Chapters 4 and 5 for specific exceptions to the allowable height in this chapter.
b. See Section 903.2 for the minimum thresholds for protection by an automatic sprinkler system for specific occupancies.
c. New Group H occupancies are required to be protected by an automatic sprinkler system in accordance with Section 903.2.5.
d. The NS value is only for use in evaluation of existing building height in accordance with the International Existing Building Code.
e. New Group I-1 and I-3 occupancies are required to be protected by an automatic sprinkler system in accordance with Section 903.2.6. For new Group I-1 occupancies, Condition 1, see Exception 1 of Section 903.2.6.
f. New and existing Group I-2 occupancies are required to be protected by an automatic sprinkler system in accordance with Section 903.2.6 and Section 1103.5 of the International Fire Code.
g. For new Group I-4 occupancies, see Exceptions 2 and 3 of Section 903.2.6.
h. New Group R occupancies are required to be protected by an automatic sprinkler system in accordance with Section 903.2.8.

Related Code Sections


2109.3.4.1 Masonry, Number of Stories
Adobe construction shall be limited to buildings not exceeding one story , except that two- story construction is allowed when designed by a registered design professional ...
Building Code 2015 of Utah > 21 Masonry > 2109 Empirical Design of Masonry > 2109.3 Adobe Construction > 2109.3.4 Detailed Requirements > 2109.3.4.1 Number of Stories
504.4 General Building Heights and Areas, Number of Stories
The maximum number of stories of a building shall not exceed the limits specified in Table 504.4. TABLE 504.4 a, b ALLOWABLE NUMBER OF STORIES ...
Building Code 2015 of Utah > 5 General Building Heights and Areas > 504 Building Height and Number of Stories > 504.4 Number of Stories
1401.6.1 Performance Compliance Methods, Building Height and Number of Stories
The value for building height and number of stories shall be the lesser value determined by the formula in Section 1401.6.1.1. Section 504 ...
Existing Building Code 2015 of Utah > 14 Performance Compliance Methods > 1401 General > 1401.6 Evaluation Process > 1401.6.1 Building Height and Number of Stories
504.2 General Building Heights and Areas, Mixed Occupancy
In a building containing mixed occupancies in accordance with Section 508, no individual occupancy shall exceed the height and number of story limits specified in this section for the applicable occupancies ...
Building Code 2015 of Utah > 5 General Building Heights and Areas > 504 Building Height and Number of Stories > 504.2 Mixed Occupancy
504.3 General Building Heights and Areas, Height in Feet
The maximum height, in feet, of a building shall not exceed the limits specified in Table 504.3. Exception: Towers, spires, steeples and other ...
Building Code 2015 of Utah > 5 General Building Heights and Areas > 504 Building Height and Number of Stories > 504.3 Height in Feet
   About UpCodes

UpCodes provides an intuitive resource to navigate building regulations.

Codes are organized by jurisdiction to help you understand which regulations apply to your project.


Find Your Codes
COMPANY INFO About Resources Contact Careers Terms Privacy
CATEGORY General New York City New York State California Codes Building Codes Online
PREMIUM Features Pricing Sign Up Log In
CODES IBC 2015 IRC 2015 IPC 2015 California Building Code 2016 Popular Sections

FOLLOW US