Code calculators: Code Calculators automatically generates a detailed list of requirements.
REFERENCE
Amendment Styling
Industry-leading search
Code diagrams
RESEARCH
Code calculators
Filter by topic
Code compare
Code sheet exports
COLLABORATION
Team projects
Bookmarks
Comments
START 2 WEEK FREE TRIAL
Have an account? Sign in
// CODE SNIPPET

Section C102 Number of Fire Hydrants

California Fire Code 2019 > C Fire Hydrant Locations and Distribution > C102 Number of Fire Hydrants
JUMP TO FULL CODE CHAPTER

C102.1 Minimum Number of Fire Hydrants for a Building

The number of fire hydrants available to a building shall be not less than the minimum specified in Table C102.1.


TABLE C102.1
REQUIRED NUMBER AND SPACING OF FIRE HYDRANTSh
FIRE-FLOW REQUIREMENT
(gpm)
MINIMUM NUMBER
OF HYDRANTS
AVERAGE SPACING
BETWEEN HYDRANTSa, b, c, f, g
(feet)
MAXIMUM DISTANCE FROM ANY
POINT ON STREET OR ROAD
FRONTAGE TO A HYDRANTd, f, g
1,750 or less 1 500 250
1,751—2,250 2 450 225
2,251—2,750 3 450 225
2,751—3,250 3 400 225
3,251—4,000 4 350 210
4,001—5,000 5 300 180
5,001—5,500 6 300 180
5,501—6,000 6 250 150
6,001—7,000 7 250 150
7,001 or more 8 or moree 200 120
For SI: 1 foot = 304.8 mm, 1 gallon per minute = 3.785 L/m.
  1. Reduce by 100 feet for dead-end streets or roads.
  2. Where streets are provided with median dividers that cannot be crossed by fire fighters pulling hose lines, or where arterial streets are provided with four or more traffic lanes and have a traffic count of more than 30,000 vehicles per day, hydrant spacing shall average 500 feet on each side of the street and be arranged on an alternating basis.
  3. Where new water mains are extended along streets where hydrants are not needed for protection of structures or similar fire problems, fire hydrants shall be provided at spacing not to exceed 1,000 feet to provide for transportation hazards.
  4. Reduce by 50 feet for dead-end streets or roads.
  5. One hydrant for each 1,000 gallons per minute or fraction thereof.
  6. A 50-percent spacing increase shall be permitted where the building is equipped throughout with an approved automatic sprinkler system in accordance with Section 903.3.1.1 of the California Fire Code.
  7. A 25-percent spacing increase shall be permitted where the building is equipped throughout with an approved automatic sprinkler system in accordance with Section 903.3.1.2 or 903.3.1.3 of the California Fire Code or Section P2904 of the California Residential Code.
  8. The fire code official is authorized to modify the location, number and distribution of fire hydrants based on site-specific constraints and hazards.

Related Code Sections


Section C102 Fire Hydrant Locations and Distribution, Number of Fire Hydrants
The number of fire hydrants available to a building shall be not less than the minimum specified in Table C102.1. TABLE C102.1 REQUIRED ...
California Fire Code 2016 > C Fire Hydrant Locations and Distribution > C102 Number of Fire Hydrants
Section C102 Fire Hydrant Locations and Distribution, Number of Fire Hydrants
The number of fire hydrants available to a building shall be not less than the minimum specified in Table C102.1. TABLE C102.1 ...
California Fire Code 2019 > C Fire Hydrant Locations and Distribution > C102 Number of Fire Hydrants
Section CC103 Fire Hydrant Locations and Distribution, Number of Fire Hydrants
The minimum number of fire hydrants available to a building shall not be less than that listed in Table CC105.1. The number of fire hydrants ...
California Fire Code 2016 > CC Fire Hydrant Locations and Distribution > CC103 Number of Fire Hydrants
Section CC103 Fire Hydrant Locations and Distribution, Number of Fire Hydrants
The minimum number of fire hydrants available to a building shall not be less than that listed in Table CC105.1. The number of fire hydrants ...
California Fire Code 2019 > CC Fire Hydrant Locations and Distribution > CC103 Number of Fire Hydrants
C103.2 Fire Hydrant Locations and Distribution, Average Spacing
to be increased by 10 percent where existing fire hydrants provide all or a portion of the required number of fire hydrants ...
California Fire Code 2016 > C Fire Hydrant Locations and Distribution > C103 Fire Hydrant Spacing > C103.2 Average Spacing
Help Contact Us Privacy Terms
Code Compare
Code Compare
Highlight differences between any two building codes.
Search
Search
Don't miss relevant code. Quickly locate sections across your jurisdiction.
Shared projects
Shared projects
Projects provide a dedicated space to collaborate on code research.
Code sheet exports
Code sheet exports
Generate a code sheet that integrates with your drawing set.
Code diagrams
Code diagrams
Unpack the code through illustrations and descriptions.
Code Calculators
Code Calculators
Code calculators automatically generate a detailed list of requirements.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
VISIT PRICING
UpCodes Premium
Leverage the full code compliance platform.
START 2 WEEK FREE TRIAL PRICING