• Codes
  • Features

    Features Overview

    Go to features
    Reference

    Reference.

    A reliable and up-to-date source of codes.
    Research

    Research.

    Rapidly and efficiently calculate project parameters.
    Collaboration

    Collaboration.

    Get everyone on the same page and streamline code research.
    Workflows
    Architects
    Architects
    General Contractors
    General Contractors
    Building Official & Plans Examiners
    Building Official & Plans Examiners
    Inspectors
    Inspectors
    Owners
    Owners
    Subcontractors
    Subcontractors
    Code Consultants
    Code Consultants
  • Pricing
  • Login
  • Sign Up
Sign Up
Login
  • Code Library
  • Features
  • Pricing
  • About
  • Careers
  • Help
  • Contact
  • Terms
  • Privacy
Sign Up
Upgrade to Premium
Code calculators: Code Calculators automatically generates a detailed list of requirements.
REFERENCE
Amendment Styling
Industry-leading search
Code diagrams
RESEARCH
Code calculators
Filter by topic
Code compare
Code sheet exports
COLLABORATION
Team projects
Bookmarks
Comments
START 2 WEEK FREE TRIAL
Have an account? Sign in
// CODE SNIPPET

314.16 Number of Conductors in Outlet, Device, and Junction Boxes, and Conduit Bodies

National Electrical Code 2020 of Illinois > 3 Wiring Methods and Materials > 314 Outlet, Device, Pull, and Junction Boxes; Conduit Bodies; Fittings; And Handhole Enclosures > 314.16 Number of Conductors in Outlet, Device, and Junction Boxes, and Conduit Bodies
JUMP TO FULL CODE CHAPTER
Boxes and conduit bodies shall be of an approved size to provide free space for all enclosed conductors. In no case shall the volume of the box, as calculated in 314.16(A), be less than the fill calculation as calculated in 314.16(B). The minimum volume for conduit bodies shall be as calculated in 314.16(C).
The provisions of this section shall not apply to terminal housings supplied with motors or generators.
Informational Note: For volume requirements of motor or generator terminal housings, see 430.12.
Boxes and conduit bodies enclosing conductors 4 AWG or larger shall also comply with the provisions of 314.28. Outlet and device boxes shall also comply with 314.24.

(A) Box Volume Calculations

The volume of a wiring enclosure (box) shall be the total volume of the assembled sections and, where used, the space provided by plaster rings, domed covers, extension rings, and so forth, that are marked with their volume or are made from boxes the dimensions of which are listed in Table 314.16(A). Where a box is provided with one or more securely installed barriers, the volume shall be apportioned to each of the resulting spaces. Each barrier, if not marked with its volume, shall be considered to take up 8.2 cm3 (1/2 in.3) if metal, and 16.4 cm3 (1.0 in.3) if nonmetallic.
Table 314.16(A) Metal Boxes
Box Trade Size Minimum Volume Maximum Number of Conductors*
(arranged by AWG size)
mm in.   cm3 in.3 18 16 14 12 10 8 6
100 × 32 (4 × 11/4) round/octagonal 205 12.5 8 7 6 5 5 5 2
100 × 38 (4 × 11/2) round/octagonal 254 15.5 10 8 7 6 6 5 3
100 × 54 (4 × 21/8) round/octagonal 353 21.5 14 12 10 9 8 7 4
100 × 32 (4 × 11/4) square 295 18.0 12 10 9 8 7 6 3
100 × 38 (4 × 11/2) square 344 21.0 14 12 10 9 8 7 4
100 × 54 (4 × 21/8) square 497 30.3 20 17 15 13 12 10 6
120 × 32 (411/16 × 11/4) square 418 25.5 17 14 12 11 10 8 5
120 × 38 (411/16 × 11/2) square 484 29.5 19 16 14 13 11 9 5
120 × 54 (411/16 × 21/8) square 689 42.0 28 24 21 18 16 14 8
75 × 50 × 38 (3 × 2 × 11/2) device 123 7.5 5 4 3 3 3 2 1
75 × 50 × 50 (3 × 2 × 2) device 164 10.0 6 5 5 4 4 3 2
75 × 50 × 57 (3 × 2 × 21/4) device 172 10.5 7 6 5 4 4 3 2
75 × 50 × 65 (3 × 2 × 21/2) device 205 12.5 8 7 6 5 5 4 2
75 × 50 × 70 (3 × 2 × 23/4) device 230 14.0 9 8 7 6 5 4 2
75 × 50 × 90 (3 × 2 × 31/2) device 295 18.0 12 10 9 8 7 6 3
100 × 54 × 38 (4 × 21/8 × 11/2) device 169 10.3 6 5 5 4 4 3 2
100 × 54 × 48 (4 × 21/8 × 17/8) device 213 13.0 8 7 6 5 5 4 2
100 × 54 × 54 (4 × 21/8 × 21/8) device 238 14.5 9 8 7 6 5 4 2
95 × 50 × 65 (33/4 × 2 × 21/2) masonry box/gang 230 14.0 9 8 7 6 5 4 2
95 × 50 × 90 (33/4 × 2 × 31/2) masonry box/gang 344 21.0 14 12 10 9 8 7 4
min. 44.5 depth FS — single cover (13/4) 221 13.5 9 7 6 6 5 4 2
min. 60.3 depth FD — single cover (23/8) 295 18.0 12 10 9 8 7 6 3
min. 44.5 depth FS — multiple cover (13/4) 295 18.0 12 10 9 8 7 6 3
min. 60.3 depth FD — multiple cover (23/8) 395 24.0 16 13 12 10 9 8 4
*Where no volume allowances are required by 314.16(B)(2) through (B)(5).

(1) Standard Boxes

The volumes of standard boxes that are not marked with their volume shall be as given in Table 314.16(A).

(2) Other Boxes

Boxes 1650 cm3 (100 in.3) or less, other than those described in Table 314.16(A), and nonmetallic boxes shall be durably and legibly marked by the manufacturer with their volume(s). Boxes described in Table 314.16(A) that have a volume larger than is designated in the table shall be permitted to have their volume marked as required by this section.

(B) Box Fill Calculations

The volumes in paragraphs 314.16(B)(1) through (B)(5), as applicable, shall be added together. No allowance shall be required for small fittings such as locknuts and bushings. Each space within a box installed with a barrier shall be calculated separately.
Table 314.16(B) Volume Allowance Required per Conductor
Size of Conductor (AWG) Free Space Within Box for Each Conductor
cm3 in.3
18 24.6 1.50
16 28.7 1.75
14 32.8 2.00
12 36.9 2.25
10 41.0 2.50
8 49.2 3.00
6 81.9 5.00

(1) Conductor Fill

Each conductor that originates outside the box and terminates or is spliced within the box shall be counted once, and each conductor that passes through the box without splice or termination shall be counted once. Each loop or coil of unbroken conductor not less than twice the minimum length required for free conductors in 300.14 shall be counted twice. The conductor fill shall be calculated using Table 314.16(B). A conductor, no part of which leaves the box, shall not be counted.
Exception: An equipment grounding conductor or conductors or not over four fixture wires smaller than 14 AWG, or both, shall be permitted to be omitted from the calculations where they enter a box from a domed luminaire or similar canopy and terminate within that box.

(2) Clamp Fill

Where one or more internal cable clamps, whether factory or field supplied, are present in the box, a single volume allowance in accordance with Table 314.16(B) shall be made based on the largest conductor present in the box. No allowance shall be required for a cable connector with its clamping mechanism outside the box.
A clamp assembly that incorporates a cable termination for the cable conductors shall be listed and marked for use with specific nonmetallic boxes. Conductors that originate within the clamp assembly shall be included in conductor fill calculations covered in 314.16(B)(1) as though they entered from outside the box. The clamp assembly shall not require a fill allowance, but the volume of the portion of the assembly that remains within the box after installation shall be excluded from the box volume as marked in 314.16(A)(2).

(3) Support Fittings Fill

Where one or more luminaire studs or hickeys are present in the box, a single volume allowance in accordance with Table 314.16(B) shall be made for each type of fitting based on the largest conductor present in the box.

(4) Device or Equipment Fill

For each yoke or strap containing one or more devices or equipment, a double volume allowance in accordance with Table 314.16(B) shall be made for each yoke or strap based on the largest conductor connected to a device(s) or equipment supported by that yoke or strap. A device or utilization equipment wider than a single 50 mm (2 in.) device box as described in Table 314.16(A) shall have double volume allowances provided for each gang required for mounting.

(5) Equipment Grounding Conductor Fill

Where up to four equipment grounding conductors or equipment bonding jumpers enter a box, a single volume allowance in accordance with Table 314.16(B) shall be made based on the largest equipment grounding conductor or equipment bonding jumper entering the box. A 1/4 volume allowance shall be made for each additional equipment grounding conductor or equipment bonding jumper that enters the box, based on the largest equipment grounding conductor or equipment bonding conductor.

(C) Conduit Bodies

(1) General

Conduit bodies enclosing 6 AWG conductors or smaller, other than short-radius conduit bodies as described in 314.16(C)(3), shall have a cross-sectional area not less than twice the cross-sectional area of the largest conduit or tubing to which they can be attached. The maximum number of conductors permitted shall be the maximum number permitted by Table 1 of Chapter 9 for the conduit or tubing to which it is attached.

(2) With Splices, Taps, or Devices

Only those conduit bodies that are durably and legibly marked by the manufacturer with their volume shall be permitted to contain splices, taps, or devices. The maximum number of conductors shall be calculated in accordance with 314.16(B). Conduit bodies shall be supported in a rigid and secure manner.

(3) Short Radius Conduit Bodies

Conduit bodies such as capped elbows and service-entrance elbows that enclose conductors 6 AWG or smaller, and are only intended to enable the installation of the raceway and the contained conductors, shall not contain splices, taps, or devices and shall be of an approved size to provide free space for all conductors enclosed in the conduit body.

Related Code Sections


314.16 Wiring Methods and Materials, Number of Conductors in Outlet, Device, and Junction Boxes, and Conduit Bodies
Boxes and conduit bodies shall be of an approved size to provide free space for all enclosed conductors. In no case shall the volume of the box ...
National Electrical Code 2020 of Illinois > 3 Wiring Methods and Materials > 314 Outlet, Device, Pull, and Junction Boxes; Conduit Bodies; Fittings; And Handhole Enclosures > 314.16 Number of Conductors in Outlet, Device, and Junction Boxes, and Conduit Bodies
314.16 Wiring Methods and Materials, Number of Conductors in Outlet, Device, and Junction Boxes, and Conduit Bodies
Boxes and conduit bodies shall be of an approved size to provide free space for all enclosed conductors. In no case shall the volume of the box ...
National Electrical Code 2017 of Illinois > 3 Wiring Methods and Materials > 314 Outlet, Device, Pull, and Junction Boxes; Conduit Bodies; Fittings; And Handhole Enclosures > 314.16 Number of Conductors in Outlet, Device, and Junction Boxes, and Conduit Bodies
(5) Wiring Methods and Materials, Equipment Grounding Conductor Fill
Where up to four equipment grounding conductors or equipment bonding jumpers enter a box, a single volume allowance in accordance with Table 314.16(B ...
National Electrical Code 2020 of Illinois > 3 Wiring Methods and Materials > 314 Outlet, Device, Pull, and Junction Boxes; Conduit Bodies; Fittings; And Handhole Enclosures > 314.16 Number of Conductors in Outlet, Device, and Junction Boxes, and Conduit Bodies > (B) Box Fill Calculations > (5) Equipment Grounding Conductor Fill
(2) Wiring Methods and Materials, Clamp Fill
with Table 314.16(B) shall be made based on the largest conductor present in the box. No allowance shall be required for a cable connector with its clamping ...
National Electrical Code 2017 of Illinois > 3 Wiring Methods and Materials > 314 Outlet, Device, Pull, and Junction Boxes; Conduit Bodies; Fittings; And Handhole Enclosures > 314.16 Number of Conductors in Outlet, Device, and Junction Boxes, and Conduit Bodies > (B) Box Fill Calculations > (2) Clamp Fill
(2) Wiring Methods and Materials, Clamp Fill
with Table 314.16(B) shall be made based on the largest conductor present in the box. No allowance shall be required for a cable connector with its clamping ...
National Electrical Code 2020 of Illinois > 3 Wiring Methods and Materials > 314 Outlet, Device, Pull, and Junction Boxes; Conduit Bodies; Fittings; And Handhole Enclosures > 314.16 Number of Conductors in Outlet, Device, and Junction Boxes, and Conduit Bodies > (B) Box Fill Calculations > (2) Clamp Fill
Help Contact Us Privacy Terms
Code sheet exports
Code sheet exports
Generate a code sheet that integrates with your drawing set.
Code Compare
Code Compare
Highlight differences between any two building codes.
Code diagrams
Code diagrams
Unpack the code through illustrations and descriptions.
Code Calculators
Code Calculators
Code calculators automatically generate a detailed list of requirements.
Search
Search
Don't miss relevant code. Quickly locate sections across your jurisdiction.
Shared projects
Shared projects
Projects provide a dedicated space to collaborate on code research.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING
UpCodes Premium
Leverage the full code compliance platform.
START 2 WEEK FREE TRIAL PRICING