907.6.4.4 Notification Zoning
JUMP TO FULL CODE CHAPTER
Upon activation of initiating devices where occupant notification is required for evacuation, all notification zones shall operate simultaneously throughout the building.
Exceptions:
- High-rise buildings as permitted in Section 907.2.13.
- Hospitals and convalescent facilities with staff alerting notification appliances or emergency voice/alarm communication, zoning shall be in accordance with the approved fire plan.
- Detention facilities.
- Upon approval by the fire code official in buildings which are sprinklered throughout, specific notification zoning shall be permitted where the notification zones are separated by a minimum of a 2-hour fire barrier and 2-hour fire-resistive floor assembly. The system shall have the capability to activate all other notification zones by automatic and manual means.
- Upon approval by the fire code official in buildings which are sprinklered throughout, specific notification zoning shall be permitted where the activated initiating device or fire extinguishing system is separated from any nonactive notification zones by a minimum of 300-ft horizontal distance. The system shall have the capability to activate all other notification zones by automatic and manual means.
- Where a Group H or L occupancy is located above the 10th story, each side of the 2-hour fire-smoke barrier shall be considered a separate zone.
Related Code Sections
23.8.6.3 Protected Premises Fire Alarm Systems, Notification Zones
Notification zones shall be consistent with the emergency response or evacuation plan for the protected premises ...
National Fire Alarm and Signaling Code 2016 of California > 23 Protected Premises Fire Alarm Systems > 23.8 System Requirements > 23.8.6 Fire Alarm System Notification Outputs > 23.8.6.3 Notification Zones
3.3.174 Definitions, Notification Zone
See 3.3.317, Zone ...
National Fire Alarm and Signaling Code 2016 of California > 3 Definitions > 3.3 General Definitions > 3.3.174 Notification Zone
907.6.4.4 Fire Protection Systems, Notification Zoning
Upon activation of initiating devices where occupant notification is required for evacuation, all notification zones shall operate simultaneously ...
California Building Code 2016 (Vol 1 & 2) > 9 Fire Protection Systems > 907 Fire Alarm and Detection Systems > 907.6 Installation and Monitoring > 907.6.4 Zones > 907.6.4.4 Notification Zoning
907.6.4.4 Fire Protection Systems, Notification Zoning
Upon activation of initiating devices where occupant notification is required for evacuation, all notification zones shall operate simultaneously ...
California Fire Code 2016 > 9 Fire Protection Systems > 907 Fire Alarm and Detection Systems > 907.6 Installation and Monitoring > 907.6.4 Zones > 907.6.4.4 Notification Zoning
907.6.4.4 Fire Protection and Life Safety Systems, Notification Zoning
Upon activation of initiating devices where occupant notification is required for evacuation, all notification zones shall operate simultaneously ...
California Fire Code 2019 > 9 Fire Protection and Life Safety Systems > 907 Fire Alarm and Detection Systems > 907.6 Installation and Monitoring > 907.6.4 Zones > 907.6.4.4 Notification Zoning