1029.14.2.4 Nosing and Profile
Related Code Sections
1029.14.2.4 Means of Egress, Nosing and Profile
Nosing and riser profile shall comply with Sections 1011.5.5 through 1011.5.5.3 ...
Building Code 2018 of Illinois > 10 Means of Egress > 1029 Assembly > 1029.14 Assembly Aisle Walking Surfaces > 1029.14.2 Stepped Aisles > 1029.14.2.4 Nosing and Profile
1030.14.2.4 Means of Egress, Nosing and Profile
Nosing and riser profile shall comply with Sections 1011.5.5 through 1011.5.5.3 ...
Building Code 2021 of Illinois > 10 Means of Egress > 1030 Assembly > 1030.14 Assembly Aisle Walking Surfaces > 1030.14.2 Stepped Aisles > 1030.14.2.4 Nosing and Profile
1011.5.5 Means of Egress, Nosing and Riser Profile
Nosings shall have a curvature or bevel of not less than 1 / 16 inch (1.6 mm) but not more than 9 / 16 inch (14.3 mm) from the foremost ...
Building Code 2021 of Illinois > 10 Means of Egress > 1011 Stairways > 1011.5 Stair Treads and Risers > 1011.5.5 Nosing and Riser Profile
1011.5.5 Means of Egress, Nosing and Riser Profile
Nosings shall have a curvature or bevel of not less than 1 / 16 inch (1.6 mm) but not more than 9 / 16 inch (14.3 mm) from the foremost ...
Building Code 2018 of Illinois > 10 Means of Egress > 1011 Stairways > 1011.5 Stair Treads and Risers > 1011.5.5 Nosing and Riser Profile
1011.5.5.3 Means of Egress, Solid Risers
Risers shall be solid. Exceptions: Solid risers are not required for stairways that are not required to comply with Section 1009.3, provided ...
Building Code 2018 of Illinois > 10 Means of Egress > 1011 Stairways > 1011.5 Stair Treads and Risers > 1011.5.5 Nosing and Riser Profile > 1011.5.5.3 Solid Risers