716.3.1.2 Nonsymmetrical Glazing Systems
JUMP TO FULL CODE CHAPTER
Nonsymmetrical fire-protection-rated glazing systems in fire partitions, fire barriers or in exterior walls with a fire separation distance of 10 feet (3048 mm) or less pursuant to Section 705 shall be tested with both faces exposed to the furnace, and the assigned fire protection rating shall be the shortest duration obtained from the two tests conducted in compliance with NFPA 257 or UL 9.
Related Code Sections
716.3.1.2 Fire and Smoke Protection Features, Nonsymmetrical Glazing Systems
Nonsymmetrical fire-protection-rated glazing systems in fire partitions , fire barriers or in exterior walls ...
Building Code 2021 of Illinois > 7 Fire and Smoke Protection Features > 716 Opening Protectives > 716.3 Fire Window Assemblies > 716.3.1 Testing Requirements > 716.3.1.2 Nonsymmetrical Glazing Systems
716.3.1.2 Fire and Smoke Protection Features, Nonsymmetrical Glazing Systems
Nonsymmetrical fire-protection-rated glazing systems in fire partitions , fire barriers or in exterior walls with a fire separation distance ...
Building Code 2018 of Illinois > 7 Fire and Smoke Protection Features > 716 Opening Protectives > 716.3 Fire Window Assemblies > 716.3.1 Testing Requirements > 716.3.1.2 Nonsymmetrical Glazing Systems
722.2.1.4.3 Fire and Smoke Protection Features, Nonsymmetrical Assemblies
For a wall without finish on one side or having different types or thicknesses of finish on each side, the calculation procedures of Sections ...
Building Code 2021 of Illinois > 7 Fire and Smoke Protection Features > 722 Calculated Fire Resistance > 722.2 Concrete Assemblies > 722.2.1 Concrete Walls > 722.2.1.4 Walls With Gypsum Wallboard or Plaster Finishes > 722.2.1.4.3 Nonsymmetrical Assemblies
722.2.1.4.3 Fire and Smoke Protection Features, Nonsymmetrical Assemblies
For a wall without finish on one side or having different types or thicknesses of finish on each side, the calculation procedures of Sections ...
Building Code 2018 of Illinois > 7 Fire and Smoke Protection Features > 722 Calculated Fire Resistance > 722.2 Concrete Assemblies > 722.2.1 Concrete Walls > 722.2.1.4 Walls With Gypsum Wallboard or Plaster Finishes > 722.2.1.4.3 Nonsymmetrical Assemblies
722.4.1.4 Fire and Smoke Protection Features, Nonsymmetrical Assemblies
For a wall without finish on one side or having different types or thicknesses of finish on each side, the calculation procedures of this section ...
Building Code 2018 of Illinois > 7 Fire and Smoke Protection Features > 722 Calculated Fire Resistance > 722.4 Clay Brick and Tile Masonry > 722.4.1 Masonry Walls > 722.4.1.4 Nonsymmetrical Assemblies