Code calculators: Code Calculators automatically generates a detailed list of requirements.
REFERENCE
Amendment Styling
Industry-leading search
Code diagrams
RESEARCH
Code calculators
Filter by topic
Code compare
Code sheet exports
COLLABORATION
Team projects
Bookmarks
Comments
START 2 WEEK FREE TRIAL
Have an account? Sign in
// CODE SNIPPET

10.1 Nonstructural Walls

California Administrative Code 2019 > 6 Seismic Evaluation Procedures for Hospital Buildings > 10 Evaluation of Elements That Are Not Part of the Lateral-Force-Resisting System > 10.1 Nonstructural Walls
JUMP TO FULL CODE CHAPTER
The term "nonstructural walls" refers to walls that are not part of the load-carrying system, but may become load bearing upon attachment and interaction with other elements. Evaluation must be made to determine if they are capable of resisting seismic forces required by Section 2.4.6 as well as the other requirements of these regulations.

10.1.1 Partitions

10.1.1.1 Masonry Partitions

There are no unbraced unreinforced masonry or hollow clay tile partitions in critical care areas, clinical laboratory service spaces, pharmaceutical service spaces, radiological service spaces, central and sterile supply areas, exit corridors, elevator shafts or stairwells.
For conforming buildings, the evaluator may consider this condition as mitigated, and no calculations are necessary. Check for the presence of support angles at floor and roof, and for spaces at the sides and top of the wall to provide for interaction of the structural system.

10.1.1.2 Structural Separations

At structural separations, partitions in exit corridors have seismic or control joints.
Check that seismic and/or control joints have been provided at structural separations. Conforming buildings that fail this check shall be placed in SPC 4.

10.1.1.3 Partition Bracing

In exit corridors, the tops of partitions that extend only to the ceiling line have lateral bracing.
For conforming buildings, the evaluator may consider this condition as mitigated, and no calculations are necessary. Partitions extending only to ceilings may overturn or buckle due to the lack of bracing.

10.1.2 Cladding and Veneer

For conforming buildings, the evaluator may consider these conditions as mitigated, and no calculations are necessary. Exterior wall panels or cladding can fall if their connections to the building frames have insufficient strength and/or ductility.

10.1.2.1 Masonry Veneer

Masonry veneer is connected to the back-up with corrosion-resistant ties spaced 24 inches on center maximum with at least one tie for every 22/3 square feet.
For conforming buildings, the evaluator may consider this condition as mitigated, and no calculations are necessary. Check for the presence of the required ties.

10.1.2.2 Cladding Panels in Moment Frame Buildings

For moment frame buildings of steel or concrete, panels are isolated from the structural frame to absorb predicted interstory drift without collapse.
For conforming buildings, the evaluator may consider this condition as mitigated, and no calculations are necessary. Check the ability of the cladding panels and their connections to tolerate the story drift computed in Section 2.4.4 without an anchorage failure.

10.1.2.3 Cladding Panel Connections

Where bearing connections are required, there are at least two bearing connections for each cladding panel and there are at least four connections for each cladding panel capable of resisting out-of-plane forces.
For conforming buildings, the evaluator may consider this condition as mitigated, and no calculations are necessary. Verify that an adequate number of the appropriate connection types are present for each cladding panel.

10.1.2.4 Cladding Panel Condition

Cladding panel connections appear to be installed properly. No connection element is severely deteriorated or corroded. There is no cracking in the panel materials indicative of substantial structural distress. There is no substantial damage to exterior cladding due to water leakage. There is no substantial damage to exterior wall cladding due to temperature movements.
Substantial deterioration can lead to loss of cladding elements or panels. Exterior walls shall be checked for deterioration. Damage due to corrosion, rotting, freezing or erosion can be concealed within the wall. Probe into the wall space, if necessary, for signs of water leakage at vulnerable interior spaces (e.g., around windows and at floor areas). Check elements that tie cladding to the backup structure and that tie the back-up structure to floor and roof slabs. Check exterior walls for cracking due to thermal movements. Check the cladding systems with appropriate reductions in member capacities. Conforming buildings that fail this check shall be placed in SPC 4.

10.1.3 Metal Stud Back-Up Systems

10.1.3.1 General

Additional steel studs frame window and door openings. Corrosion of veneer ties, tie screws, studs and stud tracks is minimal. Stud tracks are adequately fastened to the structural frame.
For conforming buildings, the evaluator may consider this condition as mitigated, and no calculations are necessary. Verify that adequate framing has been provided around openings in the exterior walls. Check the cladding systems with appropriate reductions in member capacities. Check the adequacy of the connection to the structural frame using the forces specified in Section 2.4.6.

10.1.3.2 Masonry Veneer With Stud Back-Up

Masonry veneer more than 30 feet above the ground is supported by shelf angles or other elements at each floor level. Masonry veneer is adequately anchored to the back-up at locations of through-wall flashing. Masonry veneer is connected to the back-up with corrosion-resistant ties spaced 24 inches on center maximum and with at least one tie for every 22/3 square feet.
For conforming buildings, the evaluator may consider this condition as mitigated, and no calculations are necessary. Check that adequate supports and ties are provided.

10.1.4 Masonry Veneer With Concrete Block Back-Up

10.1.4.1 General

The concrete block back-up qualifies as reinforced masonry.
For conforming buildings, the evaluator may consider this condition as mitigated, and no calculations are necessary. Verify that the concrete block back-up meets the requirements of Sections 5.3.2 and 5.3.3.

10.1.4.2 Masonry Veneer Support

Masonry veneer more than 30 feet above the ground is supported by shelf angles or other elements at each floor level. Masonry veneer is adequately anchored to the back-up at locations of through-wall flashing. Masonry veneer is connected to the back-up with corrosion-resistant ties spaced 24 inches on center maximum and with at least one tie for every 22/3 square feet. The concrete block back-up is positively anchored to the structural frame at 4-foot maximum intervals along the floors and roofs.
For conforming buildings, the evaluator may consider this condition as mitigated, and no calculations are necessary. Check that adequate supports and ties are provided.

10.1.5 Other Veneer/Panel Systems

10.1.5.1 Thin Stone Veneer Panels

Stone anchorages are adequate for computed loads.
For conforming buildings, the evaluator may consider this condition as mitigated, and no calculations are necessary. There are no visible cracks or weak veins in the stone. Check the adequacy of the connection to the stone anchorage using the forces specified in Section 2.4.6.

10.1.5.2 Wood/Aggregate Panels

There is no visible deterioration of screws or wood at panel attachment points.
The deficiency is in the strength of the connections. Determine the cause and extent of distress and check the attachment of the panels with appropriate reductions in capacity. Conforming buildings that fail this check shall be placed in SPC 4.

10.1.6 Parapets, Cornices, Ornamentation and Appendages

There are no laterally unsupported unreinforced masonry parapets or cornices above the highest anchorage level with height/ thickness ratios greater than 1.5. Concrete parapets with height/thickness ratios greater than 1.5 have vertical reinforcement. Cornices, parapets, signs and other appendages that extend above the highest anchorage level or cantilever from exterior wall faces and other exterior wall ornamentation are reinforced and well anchored to the structural system.
For conforming buildings, the evaluator may consider this condition as mitigated, and no calculations are necessary. If any of these items are of insufficient strength and/or are not securely attached to the structural elements, they may break off and fall, becoming significant life-safety hazards. Check the adequacy of these items using the forces specified in Section 2.4.6. The maximum height of an unbraced URM parapet shall be determined based on the height dimension measured above the lower of either the level of tension anchors or roof sheathing to the top of the wall parapet. The minimum height of a parapet above the wall anchor should be 12 inches.
Exception: If a reinforced concrete beam is provided at the top of the wall, the minimum height above the wall anchor may be 6 inches.

10.1.7 Means of Egress

Canopies are anchored and braced to prevent collapse and blockage of building exits.
For conforming buildings, the evaluator may consider this condition as mitigated, and no calculations are necessary. Check canopies for the forces specified in Section 2.4.6.

Related Code Sections


10.1 Seismic Evaluation Procedures for Hospital Buildings, Nonstructural Walls
The term "nonstructural walls" refers to walls that are not part of the load-carrying system, but may become load bearing upon attachment ...
California Administrative Code 2019 > 6 Seismic Evaluation Procedures for Hospital Buildings > 10 Evaluation of Elements That Are Not Part of the Lateral-Force-Resisting System > 10.1 Nonstructural Walls
10.1 Seismic Evaluation Procedures for Hospital Buildings, Nonstructural Walls
The term "nonstructural walls" refers to walls that are not part of the load-carrying system, but may become load bearing upon attachment ...
California Administrative Code 2016 > 6 Seismic Evaluation Procedures for Hospital Buildings > 10 Evaluation of Elements That Are Not Part of the Lateral-Force-Resisting System > 10.1 Nonstructural Walls
AS105.2 Strawbale Construction, Building Requirements for Use of Strawbale Nonstructural Walls
Buildings using strawbale nonstructural walls shall be subject to the following limitations and requirements: Number of stories: not more than one ...
California Residential Code 2016 > S Strawbale Construction > AS105 Strawbale Walls—General > AS105.2 Building Requirements for Use of Strawbale Nonstructural Walls
A113.8 Guidelines for the Seismic Retrofit of Existing Buildings, Nonstructural Masonry Walls
Unreinforced masonry walls that carry no design vertical or lateral loads and that are not required by the design to be part of the lateral-force ...
California Existing Building Code 2016 > A Guidelines for the Seismic Retrofit of Existing Buildings > A113 Detailed System Design Requirements > A113.8 Nonstructural Masonry Walls
A113.8 Guidelines for the Seismic Retrofit of Existing Buildings, Nonstructural Masonry Walls
Unreinforced masonry walls that do not carry design vertical or lateral loads and that are not required by the design to be part of the lateral force ...
California Existing Building Code 2019 > A Guidelines for the Seismic Retrofit of Existing Buildings > A113 Detailed Building System Design Requirements > A113.8 Nonstructural Masonry Walls
Help Contact Us Privacy Terms
Code diagrams
Code diagrams
Unpack the code through illustrations and descriptions.
Code sheet exports
Code sheet exports
Generate a code sheet that integrates with your drawing set.
Code Calculators
Code Calculators
Code calculators automatically generate a detailed list of requirements.
Code Compare
Code Compare
Highlight differences between any two building codes.
Search
Search
Don't miss relevant code. Quickly locate sections across your jurisdiction.
Shared projects
Shared projects
Projects provide a dedicated space to collaborate on code research.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
VISIT PRICING
UpCodes Premium
Leverage the full code compliance platform.
START 2 WEEK FREE TRIAL PRICING