[F] 910.3.2.3 Nonsprinklered Buildings
JUMP TO FULL CODE CHAPTER
Where installed in buildings not provided with an approved automatic sprinkler system, smoke and heat vents shall operate automatically by actuation of a heat-responsive device rated at between 100°F (38°C) and 220°F (104°C) above ambient.
Exception:
Gravity-operated drop-out vents complying with Section 910.3.2.1.
Related Code Sections
3206.10.1.2 High-Piled Combustible Storage, Nonsprinklered Buildings
Aisles in nonsprinklered buildings shall be not less than 96 inches (2438 mm) wide ...
Fire Code 2018 of South Holland > 32 High-Piled Combustible Storage > 3206 General Fire Protection and Life Safety Features > 3206.10 Aisles > 3206.10.1 Width > 3206.10.1.2 Nonsprinklered Buildings
3206.9.1.2 High-Piled Combustible Storage, Nonsprinklered Buildings
Aisles in nonsprinklered buildings shall be a minimum of 96 inches (2438 mm) wide ...
Fire Code 2012 of South Holland > 32 High-Piled Combustible Storage > 3206 General Fire Protection and Life Safety Features > 3206.9 Aisles > 3206.9.1 Width > 3206.9.1.2 Nonsprinklered Buildings
910.3.2.3 Fire Protection Systems, Nonsprinklered Buildings
Where installed in buildings not provided with an approved automatic sprinkler system, smoke and heat vents shall operate automatically by actuation ...
Building Code 2012 of South Holland > 9 Fire Protection Systems > 910 Smoke and Heat Removal > 910.3 Design and Installation > 910.3.2 Vent Operation > 910.3.2.3 Nonsprinklered Buildings
910.3.2.3 Fire Protection Systems, Nonsprinklered Buildings
Where installed in buildings not provided with an approved automatic sprinkler system, smoke and heat vents shall operate automatically by actuation ...
Fire Code 2012 of South Holland > 9 Fire Protection Systems > 910 Smoke and Heat Removal > 910.3 Design and Installation > 910.3.2 Vent Operation > 910.3.2.3 Nonsprinklered Buildings
N101.1.1 Indoor Trade Shows and Exhibitions, Nonsprinklered Buildings
In a building that is not equipped throughout with an automatic sprinkler system, the aggregate exhibit area must be less than 1,500 square feet (139 ...
Fire Code 2018 of South Holland > N Indoor Trade Shows and Exhibitions > N101 General > N101.1 Scope > N101.1.1 Nonsprinklered Buildings