// CODE SNIPPET
1104.3.2 Nonindustrial Occupancies
JUMP TO FULL CODE CHAPTER
Group A2 and B2 refrigerants shall not be used in high-probability systems where the quantity of refrigerant in any independent refrigerant circuit exceeds the amount shown in Table 1104.3.2. Group A3 and B3 refrigerants shall not be used except where approved.
Exception: This section does not apply to laboratories where the floor area per occupant is not less than 100 square feet (9.3 m2).
MAXIMUM PERMISSIBLE QUANTITIES OF REFRIGERANTS
TYPE OF REFRIGERATION SYSTEM | MAXIMUM POUNDS FOR VARIOUS OCCUPANCIES | |||
Institutional | Assembly | Residential | All other occupancies | |
Sealed absorption system | ||||
In exit access | 0 | 0 | 3.3 | 3.3 |
In adjacent outdoor locations | 0 | 0 | 22 | 22 |
In other than exit access | 0 | 6.6 | 6.6 | 6.6 |
Unit systems | ||||
In other than exit access | 0 | 0 | 6.6 | 6.6 |
For SI: 1 pound = 0.454 kg.
Related Code Sections
1104.3.2 Refrigeration, Nonindustrial Occupancies
not apply to laboratories where the floor area per occupant is not less than 100 square feet (9.3 m 2 ). TABLE 1104.3.2 MAXIMUM PERMISSIBLE ...
Mechanical Code 2018 of Maryland > 11 Refrigeration > 1104 System Application Requirements > 1104.3 Refrigerant Restrictions > 1104.3.2 Nonindustrial Occupancies
10.3 General Safety Requirements, Occupancy
shall remain in use provided that the following conditions are met: The occupancy classification remains the same. No condition deemed ...
29.4.1* Single- And Multiple-Station Alarms and Household Fire Alarm Systems, Occupants
The requirements of this chapter shall assume that occupants are not intimate with the ignition and are capable of self-rescue ...
National Fire Alarm and Signaling Code 2016 of Maryland > 29 Single- And Multiple-Station Alarms and Household Fire Alarm Systems > 29.4 Assumptions > 29.4.1* Occupants
3.3.192 Definitions, Occupancy
] An occupancy used to provide services or treatment simultaneously to four ...
State of Maryland Fire Prevention Code > 3 Definitions > 3.3 General Definitions > 3.3.192 Occupancy
3.3.196 Definitions, Occupancy
) An occupancy used to provide services or treatment simultaneously ...