714.6 Nonfire-Resistance-Rated Assemblies
JUMP TO FULL CODE CHAPTER
Penetrations of nonfire-resistance-rated floor or floor/ceiling assemblies or the ceiling membrane of a nonfire-resistance-rated roof/ceiling assembly shall meet the requirements of Section 713 or shall comply with Section 714.6.1 or 714.6.2.
Noncombustible penetrating items that connect not more than five stories are permitted, provided that the annular space is filled to resist the free passage of flame and the products of combustion with an approved noncombustible material or with a fill, void or cavity material that is tested and classified for use in through-penetration firestop systems.
Penetrating items that connect not more than two stories are permitted, provided that the annular space is filled with an approved material to resist the free passage of flame and the products of combustion.
Related Code Sections
714.6 Fire and Smoke Protection Features, Nonfire-Resistance-Rated Assemblies
Penetrations of nonfire-resistance-rated floor or floor/ceiling assemblies or the ceiling membrane of a nonfire-resistance-rated roof/ceiling ...
Building Code 2018 of Illinois > 7 Fire and Smoke Protection Features > 714 Penetrations > 714.6 Nonfire-Resistance-Rated Assemblies
717.1.2.1 Fire and Smoke Protection Features, Ducts That Penetrate Nonfire-Resistance-Rated Assemblies
The space around a duct penetrating a nonfire-resistance-rated floor assembly shall comply with Section 717.6.3 ...
Building Code 2018 of Illinois > 7 Fire and Smoke Protection Features > 717 Ducts and Air Transfer Openings > 717.1 General > 717.1.2 Ducts That Penetrate Fire-Resistance-Rated Assemblies Without Dampers > 717.1.2.1 Ducts That Penetrate Nonfire-Resistance-Rated Assemblies
707.9 Fire and Smoke Protection Features, Voids at Intersections
The voids created at the intersection of a fire barrier and a nonfire-resistance-rated roof assembly or a nonfire-resistance-rated exterior wall ...
Building Code 2018 of Illinois > 7 Fire and Smoke Protection Features > 707 Fire Barriers > 707.9 Voids at Intersections
712.1.5.2 Fire and Smoke Protection Features, Joints in or Between Nonfire-Resistance-Rated Floor Assemblies
Joints in or between floor assemblies without a required fire-resistance rating shall be permitted where they comply with one of the following ...
Building Code 2018 of Illinois > 7 Fire and Smoke Protection Features > 712 Vertical Openings > 712.1 General > 712.1.5 Joints > 712.1.5.2 Joints in or Between Nonfire-Resistance-Rated Floor Assemblies
715.4.1 Fire and Smoke Protection Features, Exterior Curtain Wall/Nonfire-Resistance-Rated Floor Assembly Intersections
Voids created at the intersection of exterior curtain wall assemblies and nonfire-resistance-rated floor or floor/ceiling assemblies shall be sealed ...
Building Code 2018 of Illinois > 7 Fire and Smoke Protection Features > 715 Fire-Resistant Joint Systems > 715.4 Exterior Curtain Wall/Floor Intersection > 715.4.1 Exterior Curtain Wall/Nonfire-Resistance-Rated Floor Assembly Intersections