1104.2.2 Nonconnecting Spaces
JUMP TO FULL CODE CHAPTER
Where a refrigerating system or part thereof is located in one or more enclosed occupied spaces that do not connect through permanent openings or HVAC ducts, the volume of the smallest occupied space shall be used to determine the refrigerant quantity limit in the system. Where different stories and floor levels connect through an open atrium or mezzanine arrangement, the volume to be used in calculating the refrigerant quantity limit shall be determined by multiplying the floor area of the lowest space by 8.2 feet (2499 mm). [ASHRAE 15:7.3.1]
Related Code Sections
1104.2.2 Refrigeration, Nonconnecting Spaces
Where a refrigerating system or part thereof is located in one or more enclosed occupied spaces that do not connect through permanent openings ...
Uniform Mechanical Code 2018 of Nevada > 11 Refrigeration > 1104.0 Requirements for Refrigerant and Refrigeration System Use > 1104.2 Refrigerant Concentration Limit > 1104.2.2 Nonconnecting Spaces
1210.2.4.1 Fuel Gas Piping, Spacing
Spacing of supports in gas piping installations shall not exceed the distance shown in Table 1210.2.4.1. Spacing of supports for CSST shall ...
Uniform Plumbing Code 2018 of Nevada > 12 Fuel Gas Piping > 1210.0 Gas Piping Installation > 1210.2 Installation of Piping > 1210.2.4 Hangers, Supports, and Anchors > 1210.2.4.1 Spacing
1310.2.4.1 Fuel Gas Piping, Spacing
Spacing of supports in gas piping installations shall not be greater than shown in Table 1310.2.4.1. Spacing of supports of CSST shall ...
Uniform Mechanical Code 2018 of Nevada > 13 Fuel Gas Piping > 1310.0 Gas Piping Installation > 1310.2 Installation of Piping > 1310.2.4 Hangers, Supports, and Anchors > 1310.2.4.1 Spacing
17.6.3.1.1* Initiating Devices, Spacing
One of the following requirements shall apply: The distance between detectors shall not exceed their listed spacing, and there shall be detectors ...
National Fire Alarm and Signaling Code 2016 of Nevada > 17 Initiating Devices > 17.6 Heat-Sensing Fire Detectors > 17.6.3 Location and Spacing > 17.6.3.1 Smooth Ceiling > 17.6.3.1.1* Spacing
17.7.6.3.3* Initiating Devices, Spacing
Smoke detector spacing shall be reduced where the airflow in a defined space exceeds 8 minutes per air change (total space volume) (equal to 7.5 air ...
National Fire Alarm and Signaling Code 2016 of Nevada > 17 Initiating Devices > 17.7 Smoke-Sensing Fire Detectors > 17.7.6 Special Considerations > 17.7.6.3 High Air Movement Areas > 17.7.6.3.3* Spacing