Unlisted nonconductive outside plant optical fiber cables shall be permitted to enter the building from the outside and shall be permitted to be installed in any of the following raceways:
  1. Intermediate metal conduit (IMC)
  2. Rigid metal conduit (RMC)
  3. Rigid polyvinyl chloride conduit (PVC)
  4. Electrical metallic tubing (EMT)
Unlisted nonconductive outside plant cables installed in rigid polyvinyl chloride conduit (PVC) or electrical metallic tubing (EMT) shall not be permitted to be installed in risers, ducts used for environmental air, plenums used for environmental air, and other spaces used for environmental air.