607.8 Noncombustible Receptacle
JUMP TO FULL CODE CHAPTER
A noncombustible receptacle shall be placed below each floor opening into the air chamber, and such receptacle shall comply with Section 607.8.1 through Section 607.8.3.
The receptacle shall be securely suspended from the floor members and shall be not more than 18 inches (457 mm) below the floor opening.
The area of the receptacle shall extend 3 inches (76 mm) beyond the opening on all sides.
The perimeter of the receptacle shall have a vertical lip not less than 1 inch (25.4 mm) high at the open sides where it is at the level of the bottom of the joists, or 3 inches (76 mm) high where the receptacle is suspended.
Related Code Sections
607.8 Duct Systems, Noncombustible Receptacle
A noncombustible receptacle shall be placed below each floor opening into the air chamber, and such receptacle shall comply with Section 607.8.1 ...
Uniform Mechanical Code 2018 of Nevada > 6 Duct Systems > 607.0 Use of Under-Floor Space as Supply Plenum for Dwelling Units > 607.8 Noncombustible Receptacle
M1601.5.3 Duct Systems, Furnace Connections
with the provisions of Section M1601.1. A noncombustible receptacle shall be installed below any floor opening into the plenum in accordance with the following ...
Residential Code 2012 of Nevada > 16 Duct Systems > M1601 Duct Construction > M1601.5 Under-Floor Plenums > M1601.5.3 Furnace Connections
M1601.5.3 Duct Systems, Furnace Connections
with the provisions of Section M1601.1. A noncombustible receptacle shall be installed below any floor opening into the plenum in accordance with the following ...
Residential Code 2018 of Nevada > 16 Duct Systems > M1601 Duct Construction > M1601.5 Under-Floor Plenums > M1601.5.3 Furnace Connections
607.0 Duct Systems, Use of Under-Floor Space as Supply Plenum for Dwelling Units
). A noncombustible receptacle shall be placed below each floor opening into the air chamber, and such receptacle shall comply with Section 607.8.1 ...
Uniform Mechanical Code 2018 of Nevada > 6 Duct Systems > 607.0 Use of Under-Floor Space as Supply Plenum for Dwelling Units
406.6 Equipment for General Use, Receptacle Faceplates (Cover Plates)
Receptacle faceplates shall be installed so as to completely cover the opening and seat against the mounting surface. Receptacle faceplates mounted ...
National Electrical Code 2017 of Nevada > 4 Equipment for General Use > 406 Receptacles, Cord Connectors, and Attachment Plugs (Caps) > 406.6 Receptacle Faceplates (Cover Plates)