// CODE SNIPPET
609.2.2 Noncircular Cross Section
JUMP TO FULL CODE CHAPTER
Grab bars with a noncircular cross section shall have a cross section dimension of 2 inches (51 mm) maximum, and a perimeter dimension of 4 inches (100 mm) minimum and 4.8 inches (120 mm) maximum.
Related Code Sections
505.7.2 General Site and Building Elements, Noncircular Cross Sections
Handrails with a noncircular cross section shall have a perimeter dimension of 4 inches (100 mm) minimum and 6 1 / 4 inches (160 mm) maximum ...
Accessible and Usable Buildings and Facilities 2009 of South Carolina > 5 General Site and Building Elements > 505 Handrails > 505.7 Cross Section > 505.7.2 Noncircular Cross Sections
505.7.2 General Site and Building Elements, Noncircular Cross Sections
Handrails with a noncircular cross section shall have a perimeter dimension of 4 inches (100 mm) minimum and 6 1 / 4 inches (160 mm) maximum ...
Accessible and Usable Buildings and Facilities 2017 of South Carolina > 5 General Site and Building Elements > 505 Handrails > 505.7 Cross Section > 505.7.2 Noncircular Cross Sections
609.2.2 Plumbing Elements and Facilities, Noncircular Cross Section
Grab bars with a noncircular cross section shall have a cross section dimension of 2 inches (51 mm) maximum, and a perimeter dimension of 4 inches ...
Accessible and Usable Buildings and Facilities 2009 of South Carolina > 6 Plumbing Elements and Facilities > 609 Grab Bars > 609.2 Cross Section > 609.2.2 Noncircular Cross Section
609.2.2 Plumbing Elements and Facilities, Noncircular Cross Section
Grab bars with a noncircular cross section shall have a cross section dimension of 2 inches (51 mm) maximum, and a perimeter dimension of 4 inches ...
Accessible and Usable Buildings and Facilities 2017 of South Carolina > 6 Plumbing Elements and Facilities > 609 Grab Bars > 609.2 Cross Section > 609.2.2 Noncircular Cross Section
(2) Special Equipment, Conduits
unlisted flexible metal conduit of noncircular cross section or trade sizes smaller than permitted by 348.20(A), or both, shall be permitted where ...
National Electrical Code 2017 of South Carolina > 6 Special Equipment > 604 Manufactured Wiring Systems > 604.100 Construction > (A) Cable or Conduit Types > (2) Conduits