  1. Non-water urinals shall not be installed in facilities that do not have provisions for necessary maintenance.
  2. Drain piping shall be sloped not less than 1/4 inch per foot to the point where it connects to piping with drainage from one or more water closets.
  3. Drain piping from non-water urinals shall not be copper to the point where it connects to piping with drainage from one or more water closets.

Related Code Sections

7.5.6 Plumbing Fixtures, Fixture Fittings and Plumbing Appliances, Non-Water Urinals
Non-water urinals shall not be installed in facilities that do not have provisions for necessary maintenance. Drain piping shall be sloped not less ...
11.3 Sanitary Drainage Systems, Drain Piping Installation
pipe size. not less than 1/16 inch per foot for 8 inch and larger pipe size. EXCEPTION: Horizontal drain piping from non-water urinals shall ...
10.21 Water Supply and Distribution Systems, Non-Potable Water Piping
Where non-potable water distribution systems are installed for irrigation, flushing water closets or urinals, or other non-potable water use ...
3.5.6 Materials, Fittings
for trenchless sewer replacement systems. Copper tube shall not be used for drainage from non-water urinals to the point where it connects to piping ...