§2706-01 Non-Production Laboratories
JUMP TO FULL CODE CHAPTER
(a) Scope. This section sets forth the standards and requirements for the storage, handling and use of hazardous materials in non-production laboratories.
(b) General Provisions. Non-production laboratories shall be designed, installed, operated and maintained in compliance with the requirements of FC2706 and this section.
(c) Design and Installation Requirements.
(1) Electrical requirements. Electrical devices, equipment and systems installed in storage rooms in non-production laboratories shall comply with the Electrical Code requirements for Class I, Group D, Division 2 locations.
(d) Operational Requirements.
(1) Signage. The entrance to each laboratory unit door shall have a conspicuously posted sign, constructed of metal or other durable material, with RED letters on a white background which shall be located in the area of the mid-point of the height of the door. Such sign shall read as follows:

Related Code Sections
419.5.1 Special Detailed Requirements Based on Use and Occupancy, Accessory Use Non-Production Laboratories
Accessory non-production laboratories occupying an area not more than 10 percent of the area of the story in which such laboratories are located ...
NYC Building Code 2008 > 4 Special Detailed Requirements Based on Use and Occupancy > 419 Non-Production Chemical Laboratories > 419.5 Classification > 419.5.1 Accessory Use Non-Production Laboratories
Section 407 Ventilation, Ventilation of Non-Production Chemical Laboratories
Non-production chemical laboratories complying with the hazardous materials quantity limitations of Section 419 of the New York City Building Code ...
419.10 Special Detailed Requirements Based on Use and Occupancy, Ventilation
Non-production laboratories shall be ventilated in accordance with Section 407 of the New York City Mechanical Code ...
NYC Building Code 2008 > 4 Special Detailed Requirements Based on Use and Occupancy > 419 Non-Production Chemical Laboratories > 419.10 Ventilation
419.6.2 Special Detailed Requirements Based on Use and Occupancy, Standpipe and Hose System
In all non-production laboratory buildings that are two or more stories above or below the grade level (level of exit discharge), standpipes shall ...
NYC Building Code 2008 > 4 Special Detailed Requirements Based on Use and Occupancy > 419 Non-Production Chemical Laboratories > 419.6 Fire Protection > 419.6.2 Standpipe and Hose System
419.4 Special Detailed Requirements Based on Use and Occupancy, Definitions
, flammability, or instability hazard rating of 2, 3, or 4 as defined in NFPA 704. LABORATORY, NON-PRODUCTION. A building or portion thereof wherein ...
NYC Building Code 2008 > 4 Special Detailed Requirements Based on Use and Occupancy > 419 Non-Production Chemical Laboratories > 419.4 Definitions