Code calculators: Code Calculators automatically generates a detailed list of requirements.
REFERENCE
Amendment Styling
Industry-leading search
Code diagrams
RESEARCH
Code calculators
Filter by topic
Code compare
Code sheet exports
COLLABORATION
Team projects
Bookmarks
Comments
START 2 WEEK FREE TRIAL
Have an account? Sign in
// CODE SNIPPET

§27-770 Noise Control of Mechanical Equipment

NYC 1968 Code (Vol I) > 12 Light, Heat, Ventilation and Noise Control > 9 Noise Control in Multiple Dwellings > §27-770 Noise Control of Mechanical Equipment
JUMP TO FULL CODE CHAPTER
  1. Minimum airborne noise insulation requirements.
    1. BOILER ROOMS. Boiler rooms adjoining dwelling spaces, either vertically or horizontally, shall be separated therefrom by floor-ceiling or partition constructions having a minimum STC rating of fifty.
    2. MECHANICAL EQUIPMENT SPACES. Spaces or shafts containing air conditioning, refrigeration, or ventilating equipment, elevator machinery, or other mechanical equipment shall be separated both vertically and horizontally from dwelling units by constructions that will provide a minimum STC rating of fifty. Spaces or shafts containing equipment totaling more than seventy-five rated h.p. shall not be located vertically or horizontally adjacent to dwelling units unless the total sound power level output of all the equipment in the space or shaft is certified not to exceed the maximum sound power levels of table 12-3 in any octave band. Such sound power level ratings shall be obtained by tests conducted in accordance with the procedures of reference standard RS 12-5.
      1. Ventilating openings into mechanical equipment spaces. Ventilating openings into boiler rooms and other mechanical equipment spaces shall not be located in yards or courts where there are windows opening from living quarters, unless such ventilating openings are provided with sound attenuating devices if needed to limit noise transmission to NC-40 (noise criterion) levels in the exposed dwelling units. For permits issued after January first, nineteen hundred seventy-two, the permissible noise levels shall not exceed NC-35.
      2. Noise criteria requirements. Noise criteria requirements prescribed in this subchapter shall be in accordance with reference standard RS 12-4.

        TABLE 12-3
        MAXIMUM SOUND POWER LEVELS PERMITTED IN MECHANICAL SPACES OR SHAFTS ADJOINING DWELLING SPACES [b]*
        Octave Bands, c.p.s.
        Mid-Frequency
        Max. Sound Power Level dba
        db re 10-13 Watts db re 10-12 Watts
        63 101 91
        125 101 91
        250 103 93
        500 105 95
        1000 102 92
        2000 101 91
        4000 98 88
        8000 96 86

        *Copy in brackets not enacted but probably intended.

        Notes for Table 12-3:
        1. aThe maximum sound power levels shall be reduced five db in any octave band where the equipment data indicate pure tone generation. The presence of pure tones may be determined by means of one-third octave band analysis. The criterion for a significant pure-tone component shall be an audible pure-tone sound together with an increase of the sound pressure level in the corresponding one-third octave band above the mean of the two adjacent one-third of at least:

          Center frequency of one-third octave band 40/125 160/250 215/500 630/1,000 1,000/10,000
          Increase in sound pressure level (db) 6 4 3 2 1 1/2
        2. bFor permits issued after January first, nineteen hundred seventy-two, the maximum sound power levels shall be changed as follows:

          Octave Bands, c.p.s. Mid-Frequency db re 10-13 Watts db re 10-12 Watts
          63 98 88
          125 97 87
          250 100 90
          1000 97 87
          2000 96 86
          4000 93 83
          8000 91 81
    3. DUCTWORK. Ducts serving dwelling units shall be lined with duct lining for at least twenty feet from the fan discharge or intake; otherwise, an approved sound attenuating device shall be installed therein. All toilet exhaust ducts shall be lined with duct lining for at least twenty feet upstream of the exhaust fan intake, otherwise, an approved sound attenuating device shall be installed therein. Duct lining shall conform to the requirements of subchapter thirteen of this chapter.
    4. EXTERIOR MECHANICAL EQUIPMENT. Mechanical equipment in a building in any occupancy group, when located outside of the building in a yard or court or on a roof, or where the equipment opens to the exterior of the building, shall be subject to the noise output limitations given in table 12-4 where one or more windows of a dwelling unit in any building in occupancy groups J-1, J-2, or J-3 is located within a sphere of one hundred foot radius whose center is any part of the equipment or its housing, unless it can be shown that the sound pressure levels, in octave bands, of the exterior mechanical equipment as measured within the dwelling unit do not exceed the levels given in table 12-5.

      TABLE 12-4
      MAXIMUM SOUND POWER LEVELS PERMITTED FOR EXTERIOR MECHANICAL EQUIPMENT ADJOINING BUILDINGSb
      Minimum Distance from Equipment to Exterior Window (ft.)a
      Maximum Sound Power Levels in Octave Bands-db re 10-13 Wattsa
      Octave Bands c.p.s. Mid Frequency
      63
      125
      250
      500
      1000
      2000
      4000
      8000
      12
      99
      92
      88
      84
      82
      82
      82
      82
      25
      103
      96
      92
      88
      86
      86
      86
      86
      50
      107
      100
      96
      92
      90
      90
      90
      90
      100
      110
      103
      99
      95
      93
      93
      93
      93
       
      in Octave Bands-db re 10-12 Watts
      12
      89
      82
      78
      74
      72
      72
      72
      72
      25
      93
      86
      82
      78
      76
      76
      76
      76
      50
      97
      90
      86
      82
      80
      80
      80
      80
      100
      100
      93
      89
      85
      83
      83
      83
      83

      Notes for Table 12-4:
      1. aThe minimum distance shall be measured in a straight line regardless of obstructions. Interpolated levels may be used for distances between those given in this table. See note a at end of table 12-3.
        1. In the event sound power level data for the exterior mechanical equipment is not available, the sound pressure levels in octave bands, of the exterior mechanical equipment shall be measured.
        2. The measurements shall be obtained with the microphone of the measuring equipment located at the interior of the dwelling unit affected in a line with the window nearest the exterior mechanical equipment. The window shall be fully open and the microphone shall be located three ft. away from the open portion of the window.
        3. Measurements shall be obtained during times when the ambient sound pressure levels, in octave bands, are at least six db lower at all octave bands than the sound pressure levels measured with the exterior equipment operating. By ambient sound pressure levels is meant the measured sound pressure levels, at the above described measuring location, with the exterior equipment not in operation.
      For permits issued after January first, nineteen hundred seventy-two, the permitted maximum sound power levels for exterior mechanical equipment adjoining buildings shall be changed as follows:

      Maximum Sound Power Levels in
      Feet
      Octave Bands-db re 10-13 Watts
       
      63
      125
      250
      500
      1000
      2000
      4000
      8000
      12
      97
      90
      83
      78
      75
      73
      72
      71
      25
      104
      96
      89
      84
      81
      79
      78
      77
      50
      110
      102
      95
      90
      87
      85
      84
      83
      100
      116
      108
      101
      96
      93
      91
      90
      89
       
      in Octave Bands-db re 10-12 Watts
      12
      87
      80
      73
      68
      65
      63
      62
      61
      25
      94
      86
      79
      74
      71
      69
      68
      67
      50
      100
      92
      85
      80
      77
      75
      74
      73
      100
      106
      98
      91
      86
      83
      81
      80
      79


      TABLE 12-5
      NOISE OUTPUT LIMITATIONS FOR EXTERIOR MECHANICAL EQUIPMENT MAXIMUM SOUND PRESSURE LEVELa,b (NOT TO BE EXCEEDED IN ANY OCTAVE BANDS)
      Octave Bands
      Center Frequency (cps)
      Decibels
      re .0002 Microbar
      63 64
      125 57
      250 51
      500 45
      1000 41
      2000 39
      4000 38
      8000 37

      Notes for Table 12-5:
      1. a Measurements shall be obtained with a sound level meter and octave band analyzer, calibrated both electronically and acoustically before and after the measurements are made. The equipment used shall meet the requirements of reference standards RS 12-6.
      2. b For permits issued after January first, nineteen hundred seventy-two, the maximum sound pressure levels shall be changed as follows:

        Octave Bands
        Center Frequencies (cps)
        Decibels
        re .0002 microbar
        63 61
        125 53
        250 46
        500 40
        1000 36
        2000 34
        4000 33
        8000 32
  2. Minimum structure-borne noise and vibration isolation requirements. All isolators used in accordance with the following requirements shall be approved.
    1. BOILER ROOMS.
      1. Boilers. All boilers supported on floors above a story having dwelling units shall be supported on resilient isolators having a minimum static deflection of one inch. The isolators shall be installed directly under the structural frame of the boiler.
      2. Boiler breeching and piping. When boilers are equipped with mechanical draft fans, the boiler breeching and piping that is supported from or on slabs, floors, or walls that are contiguous to the dwelling unit shall be supported for a distance of fifty pipe diameters on or from resilient isolators. Each isolator shall have a minimum static deflection of one inch.
    2. INCINERATOR CHARGING CHUTES.
      1. Metal chutes. Metal chutes, metal chute supports, and/or metal chute bracing, shall be free of direct contact with the shaft enclosure and the openings provided in the floor construction. Metal chutes shall be resiliently supported at each structural support location. Isolators shall provide a minimum static deflection of 0.30 in. All chutes shall be plumb.
      2. Masonry chutes. The interior chute wall shall be plumb and without obstructions for the full height of the shaft and shall have a smooth interior finish.
    3. PIPING.
      1. Metal piping connected to power driven equipment shall be resiliently supported from or on the building structure for a distance of fifty pipe diameters from the power driven equipment. The resilient isolators shall have a minimum static deflection of one inch for all piping with a four inch or larger actual outside diameter and one-half inch for piping with less than four inches in actual outside diameter. Piping connected to fluid pressure-reducing valves, shall be resiliently isolated for a distance of fifty pipe diameters from pressure reducing valves and isolators shall provide a minimum static deflection of one-half inch.
      2. Equipment such as heat exchangers, absorption refrigeration machines, etc., that is located on any floor or roof other than a floor on grade, and that is not power driven but is connected by metal piping to power driven equipment, shall be resiliently supported from or on the building structure, for a distance of fifty pipe diameters from the power driven equipment. The resilient supports shall be vibration isolators having a minimum static deflection of one inch and shall incorporate approved resilient pads having a minimum thickness of one-quarter inch.
    4. Fans. Except for fans installed in compliance with section 27-353 of article five of subchapter five of this chapter all fan equipment located on any roof or floor other than a floor on grade shall be mounted on or from vibration isolators. Fan equipment with motor drives separated from the fan equipment shall be supported on an isolated integral rigid structural base supporting both the fan and motor. Fan equipment with motor drives supported from the fan equipment shall be mounted directly on vibration isolators. Each isolator shall have provision for leveling. Isolators shall incorporate resilient pads having a minimum thickness of one-quarter inch. The vibration isolators shall provide a minimum isolator efficiency of ninety percent at fan rotor rpm with a maximum deflection of two inches. Fans and compressors of three h.p. or less assembled in unitary containers may meet this requirement with isolators internal to the container providing the isolators meet the above minimum isolator efficiencies.
    5. PUMPS. All pumps of three h. p. or more located on any floor other than a floor on grade shall be supported on vibration isolators having a minimum isolation efficiency of eighty-five per cent at the lowest disturbing frequency. Each isolator shall incorporate a leveling device and a resilient pad having a minimum thickness of one-quarter inch.
    6. COMPRESSORS. Compressors and drives located on a floor other than a floor on grade shall be mounted on vibration isolators having a minimum isolation efficiency of eighty-five per cent at the lowest disturbing frequency. Each isolator shall incorporate a leveling device and a resilient pad having a minimum thickness of one-quarter inch.
    7. COOLING TOWERS. All moving parts of cooling towers located on a roof or floor other than a floor on grade shall be installed on vibration isolators providing a minimum isolation efficiency of eighty-five per cent at fan rotor rpm with a maximum static deflection of four inches. Each isolator shall incorporate a leveling device and a resilient pad having a minimum thickness of one-quarter inch.
    8. EVAPORATIVE CONDENSERS. Evaporative and air cooled condensers located on a roof or floor other than a floor on grade shall be mounted on vibration isolators providing a minimum isolation efficiency of eighty-five per cent at fan rotor rpm with a maximum static deflection of four inches. Each isolator shall incorporate a leveling device and a resilient pad having a minimum thickness of one-quarter inch.
    9. DUCT CONNECTIONS TO FAN EQUIPMENT. Flexible connections shall be installed between fan equipment and connecting ductwork.
    10. ELEVATOR MACHINERY. Gear-driven machinery, gearless machinery, motor generators, and controllers located in an elevator machinery room or shaft on a roof, or on a floor other than a floor on grade, shall be supported on vibration isolator pads having a minimum thickness of one-half inch.
  3. Maximum permissible air velocities in ducts.
    1. DUCTS LOCATED OVER CEILINGS OF DWELLING SPACES. The maximum permissible air velocity in ductwork located over the ceilings of dwelling spaces or in masonry shafts adjoining dwelling spaces shall not exceed the velocities prescribed in table 12-6.

      TABLE 12-6
      MAXIMUM PERMISSIBLE AIR VELOCITIES IN DUCTS
      Type of System Branch Ducts Sub-Main Ducts Main Ducts
      Low Velocity 750 fpm 1000 fpm 1500 fpm
      High Velocity 1000 2000 3000


      In the application of table 12-6 the following shall apply:
      1. Any duct that connects directly to any terminal device (grille, diffuser, etc.) shall be classified as a branch duct for a distance of at least four feet from the terminal device.
      2. Any duct that connects a branch duct to a main duct or to the fan shall be classified as a sub-main duct. No duct may be classified as a sub-main duct if it connects to a terminal device by means of a connection less than four feet in length.
      3. When a duct is connected to the fan and to two or more sub-main ducts it shall be classified as a main duct.
      4. The maximum velocities shown in table 12-6 for low velocity ductwork shall apply in all cases except where a system of round ductwork is used and an acoustic air control device with self-contained attenuation components is located in the duct work prior to each air terminal device. Branch ducts, if any, connecting the acoustic air control devices to the terminals shall not have air velocities exceeding seven hundred fifty fpm. Maximum power level ratings for the acoustic air control devices shall be three db less than the values shown in table 12-7.
  4. Maximum permissible sound power levels of fan coil units, grilles, registers, diffusers and induction units. Sound power level data, in octave bands, shall be certified in accordance with the provisions of section 27-131 of article seven of subchapter one of this chapter, for grilles, registers, diffusers and induction units at design operating conditions and for coil units when operating at specified cfm. The sound power levels shall not exceed the levels listed in table 12-7 when measured in accordance with the provisions of reference standard RS 12-5.

    TABLE 12-7
    MAXIMUM PERMISSIBLE SOUND POWER LEVELS FOR TERMINAL UNITS1
    Octave Bands, c.p.s.
    Mid-Frequency
    Sound Power Levels, db
    db re
    10-13 Watts
    db re
    10-12 Watts
    63 79 69
    125 73 63
    250 67 57
    500 62 52
    1000 59 49
    2000 57 47
    4000 54 44
    8000 53 43

    Notes for Table 12-7:
    1. 1 For permits issued after January first, nineteen hundred seventy-two, the Maximum Permissible Sound Power Level for terminal units shall be changed as follows:

      Octave Bands, c.p.s.
      Mid-Frequency
      Sound Power Levels, [db]*
      db re
      10-13 Watts
      db re
      10-12 Watts
      63 76 66
      125 69 59
      250 62 52
      500 57 47
      1000 54 44
      2000 52 42
      4000 49 39
      8000 48 38

      *Copy in brackets not enacted but probably intended.

Related Code Sections


§27-770 Light, Heat, Ventilation and Noise Control, Noise Control of Mechanical Equipment
83 81 80 79 TABLE 12-5 NOISE OUTPUT LIMITATIONS FOR EXTERIOR MECHANICAL EQUIPMENT MAXIMUM SOUND PRESSURE LEVEL a,b ...
NYC 1968 Code (Vol I) > 12 Light, Heat, Ventilation and Noise Control > 9 Noise Control in Multiple Dwellings > §27-770 Noise Control of Mechanical Equipment
928.2.2 Specific Appliances, Fireplaces, Solid Fuel-Burning Equipment, and Noise Control Requirements, Operation
The operation of such exterior mechanical equipment shall comply with any applicable requirements of Sections 24-218, 24-227, 24-228 and 24-232 ...
NYC Mechanical Code 2014 > 9 Specific Appliances, Fireplaces, Solid Fuel-Burning Equipment, and Noise Control Requirements > 928 Noise Control Requirements > 928.2 Noise From Exterior Mechanical Equipment > 928.2.2 Operation
§27-776 Mechanical Ventilation, Air Conditioning, and Refrigeration Systems, General Requirements
control. Noise control requirements for mechanical equipment shall be as required by subchapter twelve of this chapter. (c) Safety. All systems ...
NYC 1968 Code (Vol I) > 13 Mechanical Ventilation, Air Conditioning, and Refrigeration Systems > 1 General > §27-776 General Requirements
313.2.2 General Regulations, Operation
The operation of such exterior mechanical equipment shall comply with any applicable requirements of Sections 24-218, 24-227, 24-228 and 24-232 ...
NYC Mechanical Code 2022 > 3 General Regulations > 313 Noise Control and Vibration Isolation Requirements > 313.2 Noise From Exterior Mechanical Equipment > 313.2.2 Operation
Section 928 Specific Appliances, Fireplaces, Solid Fuel-Burning Equipment, and Noise Control Requirements, Noise Control Requirements
Interior and exterior mechanical equipment and systems shall comply with the provisions of this section ...
NYC Mechanical Code 2014 > 9 Specific Appliances, Fireplaces, Solid Fuel-Burning Equipment, and Noise Control Requirements > 928 Noise Control Requirements
Help Contact Us Privacy Terms
Shared projects
Shared projects
Projects provide a dedicated space to collaborate on code research.
Search
Search
Don't miss relevant code. Quickly locate sections across your jurisdiction.
Code sheet exports
Code sheet exports
Generate a code sheet that integrates with your drawing set.
Code diagrams
Code diagrams
Unpack the code through illustrations and descriptions.
Code Calculators
Code Calculators
Code calculators automatically generate a detailed list of requirements.
Code Compare
Code Compare
Highlight differences between any two building codes.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
VISIT PRICING
UpCodes Premium
Leverage the full code compliance platform.
START 2 WEEK FREE TRIAL PRICING