3416A.1.1.1.1 New Hospital Buildings, Additions, Alterations, and Remodels of Conforming (SPC-3, -4, -4D, or -5) Hospital Buildings
JUMP TO FULL CODE CHAPTER
Services/systems and utilities for new hospital buildings and additions, and alterations or remodels to existing conforming buildings shall originate in hospital buildings that are conforming or have approved performance categories of SPC-3 or higher and NPC-4 or higher. The services/systems and utilities shall not pass through or under buildings that do not have approved performance categories of SPC-2 or higher and NPC-4 or higher.
Exception: Services/systems and utilities shall be permitted to pass through or under buildings that have approved nonstructural performance categories of NPC-3 or higher or NPC-2, provided that the building has an approved extension to the NPC-3 deadline. The services/systems and utilities feeding the new building addition, alteration, or remodel shall conform to the new building provisions of this code and shall be deemed by OSHPD to be free of adverse seismic interactions that could be caused by potential failure of overhead or adjacent components.
Related Code Sections
307A.1.1.1.1 Provisions for All Compliance Methods, New Hospital Buildings, Additions, Alterations, and Remodels of Conforming (SPC-3, -4, -4D, or -5) Hospital Buildings
Services/systems and utilities for new hospital buildings and additions, alterations or remodels to existing conforming buildings shall originate ...
California Existing Building Code 2019 > 3A Provisions for All Compliance Methods > 307A Compliance Alternatives for Services/Systems and Utilities > 307A.1 General > 307A.1.1 Services/Systems and Utilities > 307A.1.1.1 Services/Systems and Utilities for Hospital Buildings > 307A.1.1.1.1 New Hospital Buildings, Additions, Alterations, and Remodels of Conforming (SPC-3, -4, -4D, or -5) Hospital Buildings
3416A.1.1.1.1 Existing Structures, New Hospital Buildings, Additions, Alterations, and Remodels of Conforming (SPC-3, -4, -4D, or -5) Hospital Buildings
Services/systems and utilities for new hospital buildings and additions, and alterations or remodels to existing conforming buildings shall ...
California Building Code 2016 (Vol 1 & 2) > 34A Existing Structures > 3416A Compliance Alternatives for Services/Systems and Utilities > 3416A.1 General > 3416A.1.1 Services/Systems and Utilities > 3416A.1.1.1 Services/Systems and Utilities for Hospital Buildings > 3416A.1.1.1.1 New Hospital Buildings, Additions, Alterations, and Remodels of Conforming (SPC-3, -4, -4D, or -5) Hospital Buildings
308A.1.1 Provisions for All Compliance Methods, Means of Egress
of SPC-3 or higher, and NPC-4/NPC-4D or higher. Exception: Existing means of egress that pass through hospital buildings that have approved ...
California Existing Building Code 2019 > 3A Provisions for All Compliance Methods > 308A Compliance Alternatives for Means of Egress > 308A.1 General > 308A.1.1 Means of Egress
308A.1 Provisions for All Compliance Methods, General
shall only pass through buildings that are conforming or comply with the requirements of SPC-3 or higher, and NPC-4/NPC-4D or higher. Exception ...
California Existing Building Code 2019 > 3A Provisions for All Compliance Methods > 308A Compliance Alternatives for Means of Egress > 308A.1 General
3416A.1.1.1 Existing Structures, Services/Systems and Utilities for Hospital Buildings
Services/systems and utilities for new hospital buildings and additions, and alterations or remodels to existing conforming buildings shall ...
California Building Code 2016 (Vol 1 & 2) > 34A Existing Structures > 3416A Compliance Alternatives for Services/Systems and Utilities > 3416A.1 General > 3416A.1.1 Services/Systems and Utilities > 3416A.1.1.1 Services/Systems and Utilities for Hospital Buildings